2 Functions
2.1 Function, NC
Coil voltage disconnected
When voltage is disconnected, the armature spring (2) presses the armature (3) down against the pilot orice (4).
Pressure builds up over the diaphragm (5) via the equalizing orice (7). The diaphragm closes the main orice (6) as
soon as the pressure over the diaphragm equals the inlet pressure. The valve stays closed for as long as voltage
remains disconnected.
Coil voltage connected (open)
When voltage is applied to the coil (1), the pilot orice (4) is opened. Since the pilot orice is larger than the
equalizing orice (7), pressure over the diaphragm (5) falls and the diaphragm is lifted clear of the main orice (6).
The valve stays open for as long as the required least dierential pressure is present and voltage is applied to the
coil.
Figure 1: Function, NC
2.2 Function, NO
Coil voltage disconnected (Open)
When voltage is disconnected, the pilot orice (4) is opened. Since the pilot orice is larger than the equalizing
orice (6), pressure over the diaphragm (5) falls and the diaphragm is lifted clear of the main orice (7). The valve
stays open for as long as the required minimum dierential pressure is present and voltage is applied to the coil.
Coil voltage connected (Close)
When voltage is applied to the coil (1), the armature spring (2) presses the armature (3) down against the pilot
orice (4). Pressure builds up over the diaphragm (5) via the equalizing orice (6). The diaphragm closes the main
orice (7) as soon as the pressure over the diaphragm equals the inlet pressure. The valve stays closed for as long as
voltage remains disconnected.
© Danfoss | Climate Solutions | 2021.06 AI204086427956en-001101 | 3
Solenoid valve, Type EV220A