Product Overview

Data sheet | Electric expansion valves, type ETS 6
© Danfoss | DCS (rm) | 2019.08
AI227986437323en-000901 | 3
Nominal Capacity kW
SI units
Type
Orifice Nominal Capacity [kW]
Connec-
tion
(solder)
Valve
tube
confi-
guration
MWP MOPD
Max.
Reverse
Pressure
1)
K
V
[m
3
/h]
Code No.
[mm] R22 R134a R404A R407C R410A
A / B
[mm]
[bar] [bar] [bar]
Single pack
ETS 6 - 08 0.8 1.5 1.2 1.1 1.6 1.8 6.35 90° 47 35 20 0.011 034G5095
ETS 6 - 10 1 2.6 2 1.8 2.7 3.1 7.94 90° 47 35 35 0.030 034G5005
ETS 6 - 14 1.4 5.8 4.5 4.1 5.9 6.8 7.94 90° 47 35 20 0.052 034G5015
ETS 6 - 18
2
) 1.8 10.3 8.1 7.3 10.6 12.1 6.35 90° 47 35 28 0.082 034G5026
ETS 6 - 25 2.5 19.6 15.3 13.8 20.1 23 7.94 90° 47 35 22 0.164 034G5035
ETS 6 - 32 3.2 28.8 22.5 20.3 29.6 33.9 7.94 90° 47 28 12* 0.242 034G5055
ETS 6 - 40 4 39.1 30.6 27.6 40.2 46 7.94 90° 47 21 7 0.329 034G5065
I-pack (100 units per box)
ETS 6 - 08 0.8 1.5 1.2 1.1 1.6 1.8 6.35 90° 47 35 20 0.011 034G5090
ETS 6 - 10 1 2.6 2 1.8 2.7 3.1 7.94 90° 47 35 35 0.030 034G5000
ETS 6 - 14 1.4 5.8 4.5 4.1 5.9 6.8 7.94 90° 47 35 20 0.052 034G5010
ETS 6 - 18
2
) 1.8 10.3 8.1 7.3 10.6 12.1 6.35 90° 47 35 28 0.082 034G5024
ETS 6 - 25 2.5 19.6 15.3 13.8 20.1 23 7.94 90° 47 35 22 0.164 034G5030
ETS 6 - 32 3.2 28.8 22.5 20.3 29.6 33.9 7.94 90° 47 28 12* 0.242 034G5050
ETS 6 - 40 4 39.1 30.6 27.6 40.2 46 7.94 90° 47 21 7 0.329 034G5060
Nominal Capacity based on:
t
C
= 38 °C, t
e
= 5 °C, SC = 0 °C, SH = 0 °C
* Please contact Danfoss if higher maximum reverse pressure valve is required.
1)
Max. Reverse Pressure = Pressure as which the valve can still close tightly in reverse direction (from A to B see fig. 1).
2
) For other connection size, please contact Danfoss.
Nominal Capacity [TR]
US units
Type
Orifice Nominal Capacity [TR]
Connec-
tion
(solder)
Valve
tube
confi-
guration
MWP MOPD
Max.
Reverse
Pressure
1)
C
V
[gpm]
Code No.
[in.] R22 R134a R404A R407C R410A
A / B
[in.]
[psi] [psi] [psi]
Single pack
ETS 6 - 08
0
1
/
32
0.426 0.341 0.312 0.454 0.511
1
/
4
90° 681 507 290 0.013 034G5095
ETS 6 - 10
0
3
/
64
0.739 0.568 0.512 0.767 0.881
5
/
16
90° 681 507 507 0.035 034G5005
ETS 6 - 14
0
1
/
16
1.649 1.279 1.165 1.677 1.933
5
/
16
90° 681 507 290 0.060 034G5015
ETS 6 - 18
2
)
0
5
/
64
2.928 2.303 2.075 3.014 3.440
1
/
4
90° 681 507 406 0.099 034G5026
ETS 6 - 25
0
3
/
32
5.573 4.350 3.923 5.715 6.539
5
/
16
90° 681 507 319 0.190 034G5035
ETS 6 - 32
0
1
/
8
8.189 6.397 5.772 8.416 9.639
5
/
16
90° 681 406 174 0.280 034G5055
ETS 6 - 40
0
5
/
32
11.117 8.700 7.847 11.430 13.079
5
/
16
90° 681 304 101 0.380 034G5065
I-pack (100 units per box)
ETS 6 - 08
0
1
/
32
0.426 0.341 0.312 0.454 0.511
1
/
4
90° 681 507 290 0.013 034G5090
ETS 6 - 10
0
3
/
64
0.739 0.568 0.512 0.767 0.881
5
/
16
90° 681 507 507 0.035 034G5000
ETS 6 - 14
0
1
/
16
1.649 1.279 1.165 1.677 1.933
5
/
16
90° 681 507 290 0.060 034G5010
ETS 6 - 18
2
)
0
5
/
64
2.928 2.303 2.075 3.014 3.440
1
/
4
90° 681 507 406 0.099 034G5024
ETS 6 - 25
0
3
/
32
5.573 4.350 3.923 5.715 6.539
5
/
16
90° 681 507 319 0.190 034G5030
ETS 6 - 32
0
1
/
8
8.189 6.397 5.772 8.416 9.639
5
/
16
90° 681 406 174 0.280 034G5050
ETS 6 - 40
0
5
/
32
11.117 8.700 7.847 11.430 13.079
5
/
16
90° 681 304 101 0.380 034G5060
Nominal Capacity based on:
t
C
= 100 °F, t
e
= 41 °F, SC = 32 °F, SH = 32 °F
* Please contact Danfoss if higher maximum reverse pressure valve is required.
1)
Max. Reverse Pressure = Pressure as which the valve can still close tightly in reverse direction (from A to B see fig. 1).
2
) For other connection size, please contact Danfoss.
Valve ordering
Electric Expansion Valve
ETS 6
034G5xxx
Coil 12VDC / 3W
Made in YYY
Product designation
Type
Danfoss code no.
Technical data
Contry of origin
7061
Manufacturing
no.
034G5xxx
7061
Danfoss code no.
Manufactoring no.
Product identification
Valve
Coil