Product Overview
© Danfoss | DCS (az) | 2017.12
24h
ON
OFF
Data sheet | Solenoid valves for water shut off and leak detection, Types EV220T, EV220W, EV220B, and EV228B
IC.PD.200.S1.02 | 5
EV220W
Brass valve body, NC
Technical data
ISO228/1
connection
Seal
material
Orifice
size
K
v
-
value
Media temp.
Differential
pressure
Code no.
[mm] [m³/h] [°C] [Bar]
G 3/8 EPDM 10 1.6 0 – 100 0.3 – 10 042U4410
G 1/2 EPDM 14 4 0 – 100 0.3 – 10 042U4414
G 3/4 EPDM 18 7 0 – 100 0.3 – 10 042U4418
G 1 EPDM 22 7 0 – 100 0.3 – 10 042U4422
See separate table for AC/AZ coils
y WRAS
y RoHS Directive 2011/65/EU
y - Low Voltage Directive 2014/35/EU
- EN60730-1
- EN60730-2-8
y UL recognized
Type EV220W 10 EV220W 14 EV220W 18 EV220W 22
Time to open
[ms]
3
50 100 200 200
Time to close
[ms]
3
300 400 500 500
3
Times are indicative and apply to water. Exact times will depend on pressure conditions.
Max. working
pressure (MWP)
10 bar
Max. test pressure
EV220W 10 50 bar
EV220W 14 - EV220W 22 25 bar
Ambient temperature -40 – 50 °C
Media temperature -10 – 100
Media viscosity Max. 50 cSt
Materials
Valve body Brass W. no. 2.0401
Armature Stainless steel W. no. 1.4105 / AISI 430FR
Armature stop Stainless steel W. no. 1.4105 / AISI 430FR
Armature tube Stainless steel W. no. 1.4303 / AISI 305
Spring Stainless steel W. no. 14310 / AISI 301
O-ring EPDM
Valve plate EPDM
Diaphragm EPDM
Diaphragm valve cone Brass CW614N, W.no. 2.0401
1
) It is recommended to install a filter in front of the valve.
2
) In water applications, exercise the valves at least once every 24 hours, meaning change the state of the valve.