Product Overview
© Danfoss | DCS (az) | 2017.12
24h
ON
OFF
Data sheet | Solenoid valves for water shut off and leak detection, Types EV220T, EV220W, EV220B, and EV228B
IC.PD.200.S1.02 | 2
EV220T
Polymer valve body, NC
ISO 228-1 connection
Seal
material
Orifice
size
K
v
-
value
Media
temperature
Differential
pressure
Code no.
Inlet Outlet [mm] [m³ / h] [°C] [bar]
G ¾ ext. G ¾ ext. EPDM 14 4 0 – 85 0.3 – 10 042U8125
G ¾ ext. G ¾ ext. EPDM 18 6 0 – 85 0.3 – 10 042U8175
See separate table for AS/AZ coils.
y WRAS
y RoHS Directive 2011/65/EU
y - Low Voltage Directive 2014/35/EU
- EN60730-1
- EN60730-2-8
(Notified body by Semko)
- Pressure Equipment Directive 2014/68/EU
y UL recognized
Technical data
Type EV220T 14 EV220T 18
Time to open [ms]
3
100 200
Time to close [ms]
3
400 500
Capacity, K
v
[m
3
/h] 4 6
Capacity C
v
[gal/min] 4.7 7
3
Times are indicative and apply to water. Exact times will depend on pressure conditions
Valve
Max. working pressure (MWP) 10 bar
Max. test pressure 15 bar
Ambient temperature Max. 50 °C / 122 °F
Media viscosity 50 cSt
Materials
Body EMS Grivory HT (Glass-fiber reinforced)
Armature Stainless steel W no. 1.4105 / AISI 430FR
Armature stop Stainless steel W. no. 1.4105 / AISI 430FR
Armature tube Stainless steel W. no. 1.4303 / AISI 305
Spring Stainless steel W. no. 1.4310 / AISI 301
O-ring EPDM
Valve plate EPDM
Diaphragm EPDM
Screws Steel zinc plated delta PT
Features
Mounting Metal bracket (see dimension drawing on page 4)
Media Built-in filter mesh width 0.45 mm
1
) It is recommended to install a filter in front of the valve.
2
) In water applications, exercise the valves at least once every 24 hours, meaning change the state of the valve.
The valve exercise will minimize the risk of the valve sticking due to calcium carbonate, zinc or iron oxide build-up.