Submittal Sheet

Valve selection based on capacity calculation
As for extended capacity calculations and valve selection based on capacities and refrigerants, please refer to
Coolselector®2. Rated and extended capacities are calculated with the Coolselector®2 calculation engine to ARI
standards with the ASEREP equations based on laboratory measurements of selected valves.
Rated capacity [kW]
Table 2: Rated capacity [kW]
Type
R22/R407C
R134a
R404A/R507
R410A
R32
R290
R600a
Liquid
EVR 2
3.02
2.79
2.04
2.96
4.23
3.36
3.38
EVR 3
5.43
5.02
3.68
5.32
7.61
6.05
6.09
EVR 4
13.68
12.66
9.26
13.41
19.17
15.23
15.33
EVR 6
17.90
16.56
12.12
17.55
25.09
19.93
20.07
EVR 8
21.32
19.73
14.44
20.90
29.88
23.74
23.90
EVR 10
37.62
34.80
25.47
36.88
52.71
41.88
42.17
EVR 15
57.93
53.60
39.23
56.79
81.18
64.49
64.94
EVR 18
75.84
70.16
51.36
74.35
106.26
84.43
85.01
EVR 20
120.29
111.29
81.46
117.93
168.56
133.92
134.85
EVR 22
137.19
126.92
92.90
134.49
192.23
152.73
153.79
EVR 25
149.23
138.06
101.06
146.30
EVR 32
254.97
235.89
172.66
249.96
EVR 40
368.74
341.15
249.71
361.49
Suction vapour
EVR 2
0.33
0.24
0.29
0.42
0.54
0.41
0.23
EVR 3
0.60
0.44
0.52
0.75
0.96
0.73
0.41
EVR 4
1.51
1.10
1.32
1.90
2.43
1.85
1.03
EVR 6
1.98
1.44
1.72
2.48
3.18
2.42
1.35
EVR 8
2.35
1.71
2.05
2.96
3.78
2.88
1.60
EVR 10
4.15
3.02
3.62
5.22
6.67
5.09
2.83
EVR 15
6.40
4.65
5.57
8.03
10.28
7.83
4.36
EVR 18
8.37
6.09
7.30
10.52
13.45
10.26
5.70
EVR 20
13.28
9.66
11.57
16.68
21.34
16.27
9.04
EVR 22
15.15
11.02
13.20
19.02
24.34
18.55
10.31
EVR 25
16.33
11.79
14.25
20.58
EVR 32
27.90
20.14
24.35
35.16
EVR 40
40.35
29.12
35.21
50.85
Hot gas
EVR 2
1.35
1.04
1.10
1.65
2.18
1.54
0.94
EVR 3
2.42
1.87
1.99
2.98
3.92
2.76
1.70
EVR 4
6.10
4.70
5.01
7.50
9.86
6.96
4.28
EVR 6
7.99
6.16
6.56
9.81
12.91
9.11
5.61
EVR 8
9.51
7.33
7.81
11.68
15.37
10.85
6.68
EVR 10
16.78
12.94
13.78
20.61
27.12
19.14
11.78
EVR 15
25.85
19.93
21.22
31.74
41.77
29.48
18.14
EVR 18
33.84
26.08
27.77
41.55
54.67
38.59
23.75
EVR 20
53.68
41.37
44.05
65.91
86.72
61.21
37.67
EVR 22
61.22
47.18
50.24
75.17
98.91
69.81
42.96
EVR 25
87.87
67.73
72.12
107.91
EVR 32
150.17
115.75
123.24
184.40
EVR 40
217.22
167.43
178.27
266.74
Rated liquid and suction vapor capacity is based on:
vaporating temperature t
e
= -10 °C
liquid temperature ahead of valve t
l
= 25 °C
pressure drop in valve ∆p = 0.15 bar
Rated hot gas capacity is based on:
Solenoid valve, Type EVR 2 - EVR 40
© Danfoss | Climate Solutions | 2021.02 AI249086497583en-001301 | 6