Submittal Sheet

Media
Refrigerants
R1234yf, R1234ze(E), R125, R134a, R152a, R22, R290, R32, R404A, R407C, R407F, R407H, R410A, R413A, R417A, R422A,
R422B, R422D, R438A, R422A, R422B, R422D, R438A, R442A, R444B, R447A, R447B, R448A, R449A, R449B, R450A,
R452A, R452B, R454A, R454B, R454C, R455A, R463A, R507A, R512A, R513A, R513B, R515A, R515B, R516A, R600,
R600a.
For a complete list of approved refrigerants, visit store.danfoss.com and search for individual code numbers, where
refrigerants are listed as part of technical data.
NOTE:
Special note for R1234yf, R1234ze, R152A, R290, R32, R444B, R452B, R454A, R454B, R454C, R455A, R516A, R600 and
R600a: This product is validated in accordance to ATEX, ISO 5149, IEC 60335-2-24, IEC 60335-2-40 and UL. Ignition
risk is evaluated in accordance to ISO 5149 and IEC 60335.
The EVR 2 – EVR 22 with solder connections and without manual stem can be applied on systems with R1234yf,
R1234ze, R152A, R290, R32, R444B, R452B, R454A, R454B, R454C, R455A, R516A, R600 and R600a as the working
uid.
EVR 2-15 are connections are only approved for A1 and A2L refrigerants
NOTE:
Excluded from this EVR 22 with connections 1
3
8 inch / 35mm related to PED requirements.
The EVR 2-EVR 40 versions with solder and are connection and without manual stem can be applied to oil-free
systems : R1234ze(E)
EVR 2 - EVR 22 versions with solder and are connections and without manual stem can be applied to oil-free
systems R513A, R515B, R516A
NOTE:
EVR 2-22 (R516A) and EVR 2-40, R1234ze:
Excluded from this EVR 22 - EVR 40 with connections 1
3
8 inch / 35mm and larger connections related to higher
PED requirements.
For countries where safety standards are not an indispensable part of the safety system Danfoss recommends the
installer gets a third party approval of any system containing ammable refrigerant.
NOTE:
Please follow specic selection criteria stated in the datasheet for these particular refrigerants.
Media temperature
-40 – 105 °C, Max. 130 °C during defrosting
For R1234ze Media temperature: - 20 - 90 °C (105 °C for transient condition).
Solenoid valve, Type EVR 2 - EVR 40
© Danfoss | Climate Solutions | 2021.02 AI249086497583en-001301 | 4