Submittal Sheet
Data sheet | Solenoid coil, Types BB, BE, BF, BG, and BN
© Danfoss | DCS (rja) | 2017.06
DKRCC.PD.BS0.F7.02 | 5
Terminal box With built-in light emitting indicator diode for solenoid valves 018Z0089
DIN plug Enclosure IP65, EN 175301-803A 042N0156
Ordering
BE solenoid coil with DIN
spade and protection cap
IP20
BB solenoid coil with DIN
spade
*)
Coil with DIN plug
Type
Valve type
Tambient
[°C]
Supply
voltage
[V]
Voltage
variation
Frequency
[Hz]
Power consumption
Code no.[W] [VA]
BE024AS
EVR 2 –
EVR 40
(NC)
EVR 6 –
EVR 22
(NO)
EVRH 10 –
EVRH 40
EVRC
EVRA
EVRAT
EVRS/
EVRST
EVM (NC)
-40T80 24 -15%, +10% 50 12 21 018F6182
BE230AS
-40T80 230 -15%, +10% 50 12 22
018F6176
-40T80 220 -15%, +10% 50 11 19
BE240AS -40T80 240 -15%, +10% 50 11 19 018F6177
BE420AS -40T80 420 -15%, +10% 50 10 21 018F6179
BE115CS
-40T80 100 -15%, +10% 50 11 19
018F6185
-40T80 115 -15%, +10% 60 13 22
BE220BS -40T80 220 -15%, +10% 50 13 23 018F6189
BE110CS
-40T50 110 ±10% 50 15 28
018F6192
-40T50 110 ±10% 60 13 22
BE230CS
-40T50 220-230 ±10% 50 17 31
018F6193
-40T50 220-230 ±10% 60 14 24
Type Valve type
Tambient
[°C]
Supply
voltage
[V]
Voltage
variation
Frequency
[Hz]
Power consumption
Code no.[W] [VA]
BB024AS
EVR 2 – EVR
40 (NC)
EVR 6 – EVR
22 (NO)
EVRH 10 –
EVRH 40
EVRC
EVRA
EVRAT
EVRS/
EVRST
EVM (NC)
-40T80 24 -15%, +10% 50 11 19 018F7358
BB115AS -40T80 115 -15%, +10% 50 11 19 018F7361
BB230AS -40T80 220 - 230 -15%, +10% 50 11 19 018F7351
BB240AS -40T80 240 -15%, +10% 50 11 19 018F7352
BB024BS -40T80 24 -15%, +10% 60 14 23 018F7365
BB110CS -40T50
110 ±10% 50 15 28
018F7360
110 ±10% 60 13 22
BB230CS -40T50
220 - 230 ±10% 50 16 31
018F7363
220 - 230 ±10% 60 13 24
See „Opening differential pressure“ under „Technical data“ for the valve concerned.
When replacing a coil with terminal box, it is sufficient to change the coil unit itself. Therefore, order coil with
DIN plugs and protective cap.
*) Can only be used with DIN plug.
BN special solenoid coil with
terminal box IP67
Danfoss
18F61
Type Valve type
Tambient
[°C]
Supply
voltage
[V]
Voltage
variation
Frequency
[Hz]
Power consumption
Code no.
1
)[W] [VA]
BN024AS
EVR 2 – EVR
40 (NC)
EVR 6 – EVR
22 (NO)
EVRH 4 –
EVRH 40
EVRC/
EVRA/
EVRAT/
EVRS/
EVRST/EVM
(NC)
-40T50 24 -15%, +10% 50 24 49 018F6904
BN024BS -40T50 24 -15%, +10% 60 22 42 018F6906
BN230AS -40T50 230 -15%, +10% 50 19 43 018F6905
1
) Recommended use for EVRH with high MOPD (38 bar).
Danfoss
18F113.10
Danfoss
18F111
Danfoss
042N9038.10