Submittal Sheet
Data sheet | Solenoid coil, Types BB, BE, BF, BG, and BN
© Danfoss | DCS (rja) | 2017.06
DKRCC.PD.BS0.F7.02 | 2
Data
Solenoid coil type
1m 3-core cable
Terminal box
DIN spade and
protection cap
DIN spade
1m 3-core cable
Terminal box
DIN spade and
protection cap
DIN spade
Terminal box
IP67
BF BE BG BG BE BB BF BE BE BB BN
Enclosure IP67 IP67 IP67 IP67 IP20 IP00 IP67 IP67 IP20 IP00 IP67
Polution degree 4 4 4 4 3 3 4 4 3 3 3
Conductor area
[mm
2
]
0.75 0.75 - 1.5 0.75 - 1.5 0.75 - 1.5 0.75 - 1.5 0.75 - 1.5 0.75 0.75 - 1.5 0.75 - 1.5 0.75 - 1.5 0.75 - 1.5
Cable size [mm] Ø6.6 Ø6.0 - Ø11 Ø6.0 - Ø11 Ø6.0 - Ø11 Ø6.0 - Ø11 Ø6.0 - Ø11 Ø6.6 Ø6.0 - Ø11 Ø6.0 - Ø11 Ø6.0 - Ø11 Ø6.0 - Ø11
Rated impulse
voltage [kV], if
altitude < 4000 m
4 4 4 4 4 4 4 4 4 4 4
Humidity [R.H.] 0 − 100% 0 − 100% 0 − 100% 0 − 100%
0 − 97%
non-con-
densation
condition
0 − 97%
non-con-
densation
condition
0 − 100% 0 − 100%
0 − 97%
non-con-
densation
condition
0 − 97%
non-con-
densation
condition
0 − 100%
Type of control 1 1 1 1 1 1 1 1 1 1 1
Safety
classication
Class I Class I Class I Class I Class I Class I Class I Class I Class I Class I Class I
Max. altitude
above sea level
[m]
4000 4000 4000 4000 4000 4000 4000 4000 4000 4000 4000
Note:
For DIN plug, impulse withstand voltage is 3.1 kV for 2000 m < Altitude < 4000 m
Safety notes for ammable refrigerants (R290, R600, R600A, R32, R1234ze, and R1234yf):
1. The products (only refer to IP65/67 coils) are validated in accordance to ISO 5149, IEC 60335 (ref. IEC/EN 60079-15). Ignition risk is
evaluated in accordance to ISO 5149 and IEC 60335 (ref. IEC/EN 60079-15). See safety note below.
2. Please make sure that there is no spark, arc during the application, especially the connection of coils.
3. Follow the instruction to mount the coil correctly and apply the o-ring for sealing, to prevent the moisture penetrate inside the coils.
4. Always install a fuse ahead of the coil to avoid short circuit (fuse size should be around 2 times of rated current, and time lag: medium);
5. The coil used in an area of not more than pollution degree 2.
Safety notes:
1. The product (only refer to IP65/67 coils) can be applied on systems with R290, R600, R600A, R32, R1234ze, and R1234yf as the working uid.
2. For countries where safety standards are not an indispensable part of the safety system Danfoss recommend the installer to get a third
party approval of the system containing ammable refrigerant.
3. Note, please follow specic selection criteria stated in the datasheet for these particular refrigerants.
4. Note that the product (only refer to IP65/67 coils) has NOT been veried ATEX or IECEx or IEC 60079 series zone 2 compliant. This
product is only validated for systems in compliance with ISO5149, IEC 60335 (ref. IEC/EN 60079-15). It is the responsibility of the user
to verify such compliance. Improper use can cause explosion, re, leakage potentially causing death, personal injury, or damage to
property.
Technical data
3-core cable
The external thread in the screwed cable entry
suits exible steel hose or corresponding cable
protection (3 x 0.75 mm
2
).
Terminal box
Leads are connected to terminal screws in the
terminal box. The box is tted with a Pg 13.5
screwed entry for 6 − 14 mm cable.
Max. lead cross section: 2.5 mm
2
.
Connection DIN plugs
The three pins on the coil can be tted with spade
tabs, 6.3 mm wide (to EN175301-803A).
The two current carrying pins can also be tted
with spade tabs, 4.8 mm wide.
Max. lead cross section: 1.5 mm
2
.
Use of the protective cap supplied will prevent
inadvertent contact with live parts.
DIN socket
(to EN175301-803A)
Leads are connected in the socket. The socket is
tted with a Pg 11 screwed entry for 6 − 12 mm.
Approvals See under the required solenoid valve.