RA2000 One Pipe Steam (1PS)
Thermostatic Radiator Valve
VISXA122 © Danfoss 10/07
Prior to Installation:
The operator with valve-mounted dial and sensor must be
mounted horizontally.
IMPORTANT
In one-pipe steam systems sufcient pitch is required to permit
condensate return. Condensate should not be trapped in the
valve or vent.
Boiler/Steam supply must be cycled by a reset control and must
not run at constant pressure (which would prevent air from
entering back into the system).
Make sure that free-standing radiators or cast iron convectors are
properly pitched and that hand valves are FULLY open.
To aid in preventing overheating of rooms that are temperature
satised, boiler steam pressure must be kept low, recommended
normally at or below 2 psig. Otherwise air will be compressed in
the radiator, allowing steam to enter when not required.