Product Overview

Data sheet AVDO
Automatic By-pass Valve
VD55K622 © Danfoss 04/10
3
Fig. 1 Fig. 3
Example 1
Bypass control across heating system
Given:
System, see fi g. 1
Insignifi cant pressure loss in pipe from boiler
to bypass.
Pump characteristic, see fi g. 2.
2.2 psi (0.15 bar) system diff erential pressure
at max. system load.
Required:
Bypass circulation beginning at 2.2 psi (0.15
bar) pump pressure.
Min. 8.8 gpm (2.0 m
3
/h) boiler circulation
Seek:
A constant fl ow control that opens
simultaneously with falling load across the
system (closing radiator valves or zone valves)
A constant fl ow control that ensures min. 8.8
gpm (2.0 m
3
/h) boiler circulation at min.
system load
Solution:
An 8.8 gpm (2.0 m
3
/h) fl ow corresponds to a
3.6 psi (0.25 bar) pump pressure - see
“Capacity”.
On closing radiator valves or zone valves
AVDO ensures a minimum of 8.8 gpm
(2.0 m
3
/h) circulation at 3.6 psi (0,25 bar)
diff erential pressure across AVDO.
Choose AVDO 25 that provides 12 gpm
(2.7 m
3
/h) at 3.6 psi (0.25 bar) diff erential
pressure across valve.
Set AVDO to #1.5 (2.2 psi, 0.15 bar) opening
pressure.
Example 2
Bypass control across circulating pump
Given:
System, see fi g. 3
Pump characteristic, see fi g. 4
Required:
Bypass circulation beginning at 1.5 psi (0.1
bar) pump pressure
Max. system diff erential pressure with
closed radiator valves or zone valves must
be limited to 3.6 psi (0.25 bar)
Seek:
A constant fl ow control that opens
simultaneously with falling load across the
system (closing radiator valves or zone
valves)
A constant fl ow control that ensures max.
system diff erential pressure not to exceed
3.6 psi (0.25 bar) at min. system load
Solution:
The max. permissible diff erential pressure
3.6 psi (0.25 bar) across the system
corresponds to a 8 gpm (1.8 m
3
/h) water
volume (fi g. 4). At min. load AVDO must
ensure 8 gpm (1.8 m
3
/h) in circulation through
the bypass. In this example AVDO 20 must
be used - see “Capacity.
As circulation is not to begin before
diff erential pressure across system has
exceeded 1.5 psi (0.1 bar), AVDO is set to
# 1.0 (1.5 psi, 0.1 bar) - see “Setting.
Sizing
Fig. 2
Fig. 4