The following formulas may be used to convert to and from the SERCOS
interface units and rpm.
Vel {RPM} = Vel {cnts/CUCT * 256} * 1875 / (8 * Cnts * CUCT)
Vel {cnts/CUCT * 256} = Vel {RPM} * 8 * Cnts * CUCT / 1875
EQUATION NOTES
1) Cnts = the number of encoder (or resolver equivalent) counts per revolution.
Where: Encoder counts = Encoder lines * 4.
Resolver counts = 2^16 * MResPoles/2
2) CUCT = The control unit cycle time (IDN 1) in mS.
3) The units "CUCT/ms" is the number of CUCT periods per mS. For
example, a 2 ms CUCT has 1/2 a CUCT per 1 mS.
Remember the following when monitoring a SERCOS interface drive
through the serial port,:
1) the SERCOS interface address is also the serial MultiDrop address
2) SERCOS interface operation changes the UNITS variable to
internal units
The SERCOS interface version of the SERVOSTAR is not enabled
automatically on power-up, even with the drive address set to 0.