Installation manual

Danaher Motion Kollmorgen Wiring
SERVOSTAR
®
S and SERVOSTAR
®
CD Series 14
Non-insulated Cable Clamp
The following figures shows how cable bonding is implemented using non-
insulated metallic cable clamps.
Sx
Cx
From the drive
Terminal Strip
To Motor
Bonded to Back
Plane
Sx Drive Clamp Cx Drive Clamp Terminal Clamp
Alternative Bonding Methods
Another option is to use cable bonding clamps offered by Phoenix Contact (and
others). When using the Phoenix Contact parts, make sure that a low impedance
(high frequency) ground is connected from the ground bus bar to the back panel.
This can be done with a flat braid or a copper bus bar. The SK parts from
Phoenix (SK8, SK14, & SK20) slide onto the bus bar. The cable (with exposed
shield) is inserted through the SK piece and the thumbscrew on top of the SK
piece is used to tighten the connection between the cable shield and the bus bar.
Phoenix Contact Part # Description Cable Diameter Range
3025163
Type SK8
Shielded terminal block - for
placing the shield on bus bars.
SK8
up to 8mm or 0.315 in
3025176
TypeSK14
Shielded terminal block - for
placing the shield on bus bars.
SK14
8mm to 14mm or 0.551 in
3025189
Type SK20
Shielded terminal block - for
placing the shield on bus bars.
SK20
14mm to 20mm or 0.787 in
0404428
Type AB/SS
Support for bus bar. 2 needed to
mount ground bus.
N/A
0402174
Type NLS-CU 3/10
Bus bar material - 10mm x 3mm
copper at varying lengths.
N/A