Product manual

Danaher Motion 05/2008 Specifications
S200-VTS Product Manual 13
3.2.5 AC Control Power Inrush Current & Fusing
Worse Case Inrush Peak Current at 240 VAC
10 A 0-p
Inrush Pulse Width
1.60 ms
Fusing – Control Inputs
Bussmann MDA – 1/2
Nominal Power draw
Base: 7 W
With Option Card: 10 W
3.2.6 AC Power On Delay
Control Power Applied to Drive Operational
1.25 seconds
Bus Power To Full Bus On Soft Start Units
1.0 seconds
3.3 DC Input Drives - Control and Power
3.3.1 DC Control Power Supply
Control Voltage Range (VDC)
(J1-1 to J1-2)
+10 to +90
Control Input Power (watts)
1
2 to 8
1
(20 watt min supply recommended) Refer to the DC Power Supply Section
for detailed application information and requirements.
3.3.2 DC Bus Voltage and Faults
+BUS Voltage Range (VDC) (J1-3 to J1-2)
+20 to +90
+BUS Undervoltage Fault
+17 VDC nominal
+BUS Overvoltage Fault
+91 VDC nominal
3.3.3 DC Control Power On Delay
Control Power Applied to Drive Operational
1.5 seconds
3.4 Motor Current Control
Motor Phase Current Waveform
(In Sine or six-step mode output torque = Motor
K
T
*Drive I
FB
)
Pure sinusoidal or six-step,
depending on feedback
device
Motor Shaft Torque (Ignoring motor magnetic saturation)
Peak (hot motor winding)
Multiply K
T
by 1.06 for cold motor winding (AKM
or PMA motors).
K
T
(N-m/ARMS)*Drive
Ipeak (ARMS)
Instantaneous
K
T
(N-m/ARMS)*IFB
(ARMS)