4.2 INPUT POWER SPECIFICATIONS
AC Motor Power Supply
Input Voltage Range (RMS) VAC 90 to 265
Phases 1 or 3
Transformer Suggested KVA 2 to 3
Maximum AC Line KVA
1
100
1
Maximum AC Line is specified to limit the mains surges to the drive.
AC Bus Voltage and Faults
240 VAC Input Nominal Bus Voltage 320 VDC
120 VAC Input Nominal Bus Voltage 155 VDC
BUS Under voltage Fault Factory Default is None
BUS Over voltage (BusOV) Fault 407 VDC + 5%
BUS Regen Voltage = 0.974*BusOV = 397 VDC Nominal
AC Inrush Current & Fusing
Worse Case Inrush Peak Current at 240 VAC 140 A 0-p
Inrush pulse width 1.5 ms
Recommended Fusing Line Inputs
Type – 250 VAC Time Delay Fuse
S20260 S20360 S20660 S21260
240 VAC 3 Phase
(A
RMS
)
FRN-R-5 FRN-R-8 FRNR-15 FRN-R-25
240 VAC 1 Phase
(A
RMS
)
FRN-R-5 FRN-R-10 FRN-R-20 FRN-R-30
120 VAC 1 Phase
(A
RMS
)
FRN-R-5 FRN-R-10 FRN-R-20
-
AC Power on Delay
Control Power Applied to Drive Operational 1.25 seconds
AC Control Power Supply
85 VAC to 265 VAC single phase
47 to 63 Hz
Input Voltage Range (RMS)
120 VDC to 375 VDC
85 VAC 60 Hz > 0.78 60 Hz cycles
120 VAC 60 Hz > 3.3 60 Hz cycles
Ride Through Time for AC Line Drop
240 VAC 60 Hz >18.5 60 Hz cycles