Data sheet 08/13-LC007-8
LED control gear
Compact dimming
Wiring guidelines
•The cables should be run separately from the mains connections and mains
cables to ensure good EMC conditions.
•The maximum secondary cable length at the terminals is 5 m. The LED wiring
should be kept as short as possible to ensure good EMC.
•The LED control gear does not have polarity reversal protection on the second-
ary side. LED modules that do not have polarity reversal protection may be
damaged if polarity is reversed.
5.5 – 6.5 mm
wire preparation:
0.5 – 2.5 mm²
Wiring type and cross section
Strain relief for Ø 3 – 8 mm.
Information about the correct handling of LEDs can be found in the
u brochure
“Installation instructions and guidelines” Ê www.tridonic.com
NTC value Start operation temperature
(3 V Req = 26 kΩ)
Total switch-o temperature
(2,2 V Ro = 15 kΩ)
100 K 55 °C 72 °C
150 K 65 °C 80 °C
220 K 75 °C 90 °C
Component tolerances are not considered.
4.5 – 5.5 mm
wire preparation:
0.2 – 1.5 mm²
8.5 – 9.5 mm
wire preparation:
0.5 – 2.5 mm²
1...10 V/NTC / FAN
PUSH / DA
Maximum loading of automatic circuit breakers
Automatic circuit breaker type C10 C16 B10 B16
Installation Ø 1.5 mm
2
1.5 mm
2
1.5 mm
2
1.5 mm
2
LCAI 050/1050 N020 DALI 15 25 9 15
Input / Output terminal
Please use only one wire per terminal.
In DALI operation a failure of the lamp can be communicated by short-circuiting
the NTC port or by leaving it open (DALI command: QUERY FAILURE STATUS).
In case of an open/short-circuit at the NTC input, the unit will identify a lamp
fault. At an LED module or NTC temperature of 75 °C, there will be a voltage
drop of 3 V and/or a resistance value of 26 kOhm. From an LED module or NTV
temperature of 90 °C, there will be 2.2 V / 15 kOhm and the LED control gear
will switch off.
If no NTC resistance is connected and the “lamp fault” message (DALI com-
mand: QUERY FAILURE STATUS) is not required, a resistance of only 220 kOhm
has to be connected.
Short/soft start mode
The soft start mode is enabled/disabled by pressing a momentary-action switch
at the Push L input, while mains voltage is applied to the LED control gear. The
LED control gear will then operate in soft and/or short start mode.
Short start mode between 1 – 100 % < 0.7 s: default setting
Soft start mode between 1 – 100 % > 1.5 s
PUSH
PUSH
L
PRI
N
L
Thermic sensor
If a temperature sensor is to be used either the preinstalled resistor in the NTC
terminal or the “JP51” jumper must be removed, depending on the device versi-
on. A temperature sensor can then be connected.
Connector for the synchronisation cable
SPOX from Molex
•Plug for cable (art. no. Molex: 0022433020)
PHASED OUT