Technical data

QUICKTRONIC
®
Intelligent DALI DIM | Tender documents
43
8 Tender documents
QUICKTRONIC
®
Intelligent DALI DIM for compact
uorescent lamps
Order reference depending on the type of lamp:
QTi DALI T/E … DIM
Intelligent ECG with DALI interface according to IEC
60929
OSRAM DULUX
®
T/E 18, 26, 32, 42 W and OSRAM
DULUX
®
compact fl uorescent lamps
T/E CONSTANT 26, 32, 42 W (amalgam lamps) with
dimming from 3 % to 100 %
Warm start of the lamp within 0.6 seconds without igni-
tion fl ash
Manual dimming operation (Touch DIM) without any
control unit with standard installation push-button, incl.
memory function (double-click) and soft start
Lifetime: 80,000 h at t
c
= 75 °C and a max. failure rate of
10 %
Effective overtemperature protection of the DIM ECG
through intelligent power reduction at high t
c
tempera-
tures
5-year System
+
guarantee: There is a replacement for
every ECG that fails due to a material or manufacturer
defect, according to the conditions under
www.osram.com/guarantee
CELMA energy classi cation EEI = A1 BAT
Highest energy ef ciency thanks to cut-off technology
EoL shutdown according to EN/IEC 61347-2-3, section 17
For use in emergency lighting systems according to
EN 50172/DIN VDE 0108-100
Emergency power properties can be confi gured, light
value can be set without control signal between 100 %
and 3 % luminous fl ux.
Quality marks: ENEC, VDE, EMV
EN 60929, EN 61347-2-3, EN 55015, EN 61000-3-2,
EN 61547, EN 61000-3-3
QUICKTRONIC
®
Intelligent DALI DIM for
T5-16-mm fl uorescent lamps
Order reference depending on the type of lamp:
QTi DALI … DIM
Intelligent ECG with DALI interface according to IEC
60929
Operation of T5-16-mm fl uorescent lamps of the
same length in a single luminaire to fl exibly adjust the
level of light
Dimming from 1 % to 100 %
Max. dimming speed for dynamic RGB color light appli-
cation 5 ms, from 1 % to 100 % through optimized con-
trol of the fi lament heating
Warm start of the lamp within 0.5 seconds without igni-
tion fl ash
Manual dimming operation (Touch DIM) without any
control unit with standard installation push-button, incl.
memory function (double-click) and soft start
Lifetime: 80,000 h at t
c
= 75 °C and a max. failure rate of
10 %
Effective overtemperature protection of the DIM ECG
through intelligent power reduction at high t
c
tempera-
tures
5-year System
+
guarantee: There is a replacement for
every ECG that fails due to a material or manufacturer
defect, according to the conditions under
www.osram.com/guarantee
CELMA energy classi cation EEI = A1 BAT
Highest energy ef ciency thanks to cut-off technology
EoL shutdown according to EN/IEC 61347-2-3, section 17
For use in emergency lighting systems according to
EN 50172/DIN VDE 0108-100
Emergency power properties can be confi gured, light
value can be set without control signal between 100 %
and 1 % luminous fl ux.
Quality marks: ENEC, VDE, EMV
EN 60929, EN 61347-2-3, EN 55015, EN 61000-3-2,
EN 61547, EN 61000-3-3
QUICKTRONIC
®
Intelligent DALI DIM for
T8-Ø-26-mm fl uorescent lamps
Order reference depending on the type of lamp:
QTi DALI … DIM
Intelligent ECG with DALI interface according to IEC
60929
Commercially-available T8-Ø-26-mm fl uorescent lamps
with dimming from 1 % to 100 %
Max. dimming speed for dynamic RGB color light appli-
cation 5 ms, from 1 % to 100 % through optimized con-
trol of the fi lament heating
Warm start of the lamp within 0.5 seconds without igni-
tion fl ash
Manual dimming operation (Touch DIM) without any
control unit with standard installation push-button,
incl. memory function (double-click) and soft start
Lifetime: 100,000 h at t
c
= 75 °C and a max. failure rate
of 10 %
Effective overtemperature protection of the DIM ECG
through intelligent power reduction at high t
c
tempera-
tures
5-year System
+
guarantee: There is a replacement for
every ECG that fails due to a material or manufacturer
defect, according to the conditions under
www.osram.com/guarantee
CELMA energy classi cation EEI = A1 BAT
Highest energy ef ciency thanks to cut-off technology
EoL shutdown according to EN/IEC 61347-2-3, section 17
For use in emergency lighting systems according to
EN 50172/DIN VDE 0108-100
Emergency power properties can be confi gured, light
value can be set without control signal between 100 %
and 1 % luminous fl ux.
Quality marks: ENEC, VDE, EMV
EN 60929, EN 61347-2-3, EN 55015, EN 61000-3-2,
EN 61547, EN 61000-3-3