Technical data

QUICKTRONIC
®
Intelligent DALI DIM | Additional properties of dimmable control gears from OSRAM
32
4.7.1 Pressing in and loosening the connection cables
Manual contact of the insulation displacement termination
(above) with the insertion tool, e.g. order number:
WAGO 206-831
Loosen the plug contacts (below) with the WAGO 206-830
extraction tool.
Alternatively, the plug contact can be extracted by
simultaneously turning and pulling.
Information about wire stripping and cable cross sections
are printed on the device.
4.7.2 Cable cross sections
4.7.3 Basic insulation
The IEC 61347 requires basic insulation for control inputs
between the control circuit and mains. The DALI standard
(IEC 62386) references this. Thus, the DALI line has “only”
basic insulation and must, therefore, be treated like a mains
voltage. The same is true of the 110-V interface.
4.7.4 Sockets
The lamps must fi t tightly and make contact in the lamp
sockets. The sockets must be selected depending on the
ECG/type of lamp used.
4.7.5 Master/slave circuit
Additional wiring of the lamp cable to the next luminaire.
Master/slave operation is not allowed with multi-lamp dim-
ming devices. The reason for this are capacitive leakage
currents, which can lead to asymmetries, differing lumi-
nances and instable dimming operation (fl ickering).
4.7.6 Minimum refl ector distances
The refl ector may never rest against to the lamp as this may
otherwise cause vibrations and noise. In all luminaires, a
minimum distance of 6 mm must be maintained between
the lamp and the refl ector and other luminaire parts. If the
distance is shorter, uneven brightness can occur along the
lamp due to capacitive leakage currents. Flickering can al-
so occur. Moreover, lamp parts which touch the bulbs can
lead to mercury bonds in the lamps.
Wago insertion tool
Wago extraction tool
Loosening the plug contact
Typical cable cross sections of pin and insulation
displacement connectors (IDCs)
Single-strand wire Multi-strand wire
IDC (insulation dis-
placement connector)
max. 0.5 m max. 0,75 m
Plug contact 0.5…1.0 mm² 0.5…1.0 mm²
(with wire-end ferrule)
Plug terminal 0.5…1.5 mm² 0.5…1.5 mm²
(with wire-end ferrule)
1.
1. Insert the extraction tool above the wire
into the wire entry point
2. Pull out the wire
2.