Technical data
QUICKTRONIC
®
Intelligent DALI DIM | Additional properties of dimmable control gears from OSRAM
31
a) Upper limitation
The easiest way to achieve this is parallel switching of a
Zener diode with the corresponding value. A Zener diode
with a nominal value of 7 V must be used when limiting, for
example, to 7 V. Model Bzx 55C xVx can be recommended.
For xVx, for example, 7V5 equals 7.5 V. At least 20 ECGs
can be controlled with this model. In principle, the control
unit with the lowest value sets the specifi cation for the
OSRAM DIM ECG when running parallel switching for mul-
tiple control units. This applies to all passive control units,
i. e. devices which represent a current sink.
b) Lower limitation
An effective lower limitation can be achieved through serial
switching of two control units. The sum of both devices is
effective. With one device, the control voltage specifi cation
of the other device cannot be exceeded. Caution: The
smallest achievable control voltage amounts to approx. 2 V
(c. 4 % luminous fl ux) when serially switching two control
units. The connections are to be made according to the
sketch.
4.6.3 Line length of the 1…10-V control line
The control line lengths are only limited by a drop in the
voltage. Overall, it can be said that a 100-m line length is
generally noncritical. The following formula can be used for
a more precise estimation:
e. g. at 1.5 mm², lighting strip, feed-in to start:
L
max
= 35 km/number of ECGs
= 350 m with 100 ECGs
= 700 m with 50 ECGs
Any line length may be used with DIM SA signal amplifi ers.
4.6.4 1…10-V DIM ECGs and emergency lighting
Dimmable 1…10-V QUICKTRONIC
®
ECGs are suitable for
emergency lighting systems according to DIN V VDE V
0108-100 and DIN EN 50172. When using dimmable 1…10-
V QUICKTRONIC
®
ECGs in emergency lighting systems,
the control line should be disrupted in emergency operation
by suitable measures at the positive terminal. Correspond-
ing easy-to-wire toggle converters are available on the mar-
ket which send an adjustable control voltage to the OS-
RAM DIM ECG, thus enabling battery-friendly emergency
lighting operation at less than 100 % luminous fl ux.
Some accessory components (e. g. DIM SA, DIM ICM 10
signal amplifi ers) are not approved for battery operation.
Therefore, it must be ensured that these components are
never switched to a DC source. The signal amplifi er, for ex-
ample, represents in this case a fi xed resistor which is con-
nected to the control line. The dimmer setting of an ECG is
then about 20 %, and higher with more ECGs.
4.7 Terminals/cable cross sections/insulation
stripping length
Both single-core wires and fl exible ones are permissible
for combination terminals for T5 and T8 fl uorescent lamps
used in the QTi DALI/DIM. The terminal can be contacted
above via a so-called IDC (insulation displacement connec-
tor) and below via a plug contact (wire stripping 8.5–11 mm).
For ECGs with plug terminals (HF DIM, QTi T/E DALI/DIM),
both single-core wires (wire stripping 8.5–9.5 mm) and
fl exible ones are permissible, provided they are zinc-plated,
sound-welded or equipped with wire-end ferrules.
Limiting top control voltage
Limiting bottom control voltage
Control unit
Control unit 1
Control unit 2
DIM ECG
DIM ECG
DIM ECG
DIM ECG
+
+
+
+
+
+
+
+
+
–
–
–
–
–
–
–
–
–
Zener diode
Additional ECGs
Additional ECGs
Emergency lighting with OSRAM 1…10-V DIM ECGs
Switching from AC to DC (incl. plus terminal)
AC DC
1…10-V emer-
gency lighting
1…10-V normal
++––
DIM ECG
~
~
–
~
+
–