Technical data
QUICKTRONIC
®
Intelligent DALI DIM | Additional properties of dimmable control gears from OSRAM
23
4.2.3.1 Operating parameters for Touch DIM and
Corridor functionality
AC voltages of 10…230 V (effective value) with a frequency
of 48...63 Hz must be used for operating Touch DIM and
Corridor functionalities – not DC voltage.
4.2.3.2 Interference compensation (for wiring > 25 m)
Above a total cable length of 25 m to 100 m from the push-
button to the ECG, a control transformer according to both
of the following diagrams must be used to prevent malfunc-
tions (e. g. through capacitive couplings): Primary 230 V/
secondary 12 V, required transformer power: 25 mW per
connected ECG (i. e. 150 mW with 6 ECGs, 2 mA control
current per ECG).
Furthermore, there is the opportunity to switch a conven-
tional resistor (1 W, 150 k) to compensate for interference
(damping of the line) between phase and neutral wire,
which is illustrated in the following diagram.
Control transformer for compensation near the ECG
(e. g. in a luminaire)
Control transformer near the push-button (e. g. in the
SD (sub-distributor) or a FTB (flush-type box)).
12-V transformer
min. power: 25 mW x ECG quantity
12-V transformer
min. power: 25 mW x ECG quantity
L
L
N
N
PE
PE
DALI ECG
~
~
DA
DA
Installation cable
Push-
button
Push-
button
Installation cable
DALI ECG
~
~
DA
DA
Compensation for the connecting cable through a resistor (1 W, 150 kΩ)
12)
L
Max. 50 m total line length with
compensation of the connecting cable
R: 150 k, 1 W
N
12) E. g.: Vishay Beyschlag: MBA/SMA 0204, MBB/SMA 0207, MBE/
SMA 0414 - Professional