Technical data

QUICKTRONIC
®
Intelligent DALI DIM | Additional properties of dimmable control gears from OSRAM
22
4.2.3 Wiring and cable compensation
The cable length between the push-button and the far-
thest DALI ECG may not be longer than 25 meters.
Compensation measures must be applied for line
lengths required to be more than 25 meters long (bell
transformer, resistance).
Do not use more than 20 DALI ECGs in a single Touch
DIM application (up to 20 ECGs can be controlled by
one push-button). The greater the number of DALI ECGs
controlled simultaneously, the greater the risk of
asynchronisms (see 3.2.6.2).
Differing lamp families should not be mixed due to dif-
ferent preheating times (e.g. T5-HO lamps (500 ms start
time) vs. T5-HE lamps (700 ms start time)).
Multiple control points are possible, provided the total
line length of 25 m is not exceeded.
Touch DIM sensor: No more than four DALI ECGs
may be operated with a single Touch DIM sensor.
Maximum cable length (distance sensor/DALI ECG)
is 10 meters.
The Touch DIM wiring and the operator button must be
rated for mains voltage (230 V).
Operation via push-button
L3
T
Push-
button
PE N L1 L2 L3
L2
L1
N
PE
Lamp
OSRAM DALI ECG
OSRAM DALI ECG
OSRAM DALI ECG
Lamp
Lamp
~
~
~
~
~
~
DA
DA
DA
1
1
1
2
2
2
3
3
3
4
4
4
DA
DA
DA