Technical data
QUICKTRONIC
®
Intelligent DALI DIM | Additional properties of dimmable control gears from OSRAM
22
4.2.3 Wiring and cable compensation
— The cable length between the push-button and the far-
thest DALI ECG may not be longer than 25 meters.
Compensation measures must be applied for line
lengths required to be more than 25 meters long (bell
transformer, resistance).
— Do not use more than 20 DALI ECGs in a single Touch
DIM application (up to 20 ECGs can be controlled by
one push-button). The greater the number of DALI ECGs
controlled simultaneously, the greater the risk of
asynchronisms (see 3.2.6.2).
— Differing lamp families should not be mixed due to dif-
ferent preheating times (e.g. T5-HO lamps (500 ms start
time) vs. T5-HE lamps (700 ms start time)).
— Multiple control points are possible, provided the total
line length of 25 m is not exceeded.
— Touch DIM sensor: No more than four DALI ECGs
may be operated with a single Touch DIM sensor.
Maximum cable length (distance sensor/DALI ECG)
is 10 meters.
— The Touch DIM wiring and the operator button must be
rated for mains voltage (230 V).
Operation via push-button
L3
T
Push-
button
PE N L1 L2 L3
L2
L1
N
PE
Lamp
OSRAM DALI ECG
OSRAM DALI ECG
OSRAM DALI ECG
Lamp
Lamp
~
~
~
~
~
~
DA
DA
DA
1
1
1
2
2
2
3
3
3
4
4
4
DA
DA
DA