Technical data

QUICKTRONIC
®
Intelligent DALI DIM | Additional properties of dimmable control gears from OSRAM
20
4 Additional properties of dimmable
control gears from OSRAM
8)
4.1 OSRAM DALI/110-V ECGs:
Added value through intelligent features
Automatic lamp detection through intelligent multi-lamp
operation (reduction of the ECG range of models)
Lamps of the same length and various outputs can
be operated on a single ECG. Furthermore, special
approvals exist for certain lamp/ECG combinations.
9)
Dimming range up to 1 % of the nominal luminous fl ux
(3 % in the case of CFL, also HF DIM)
Ignition of the lamp at -25 °C ambient temperature
Optimized lamp warm start within 0.6 s (also HF DIM )
Temperature-dependent “cut-off” in case of dimmer
settings > 80 %
Shutting down the fi lament heating at dimmer set-
tings > 80 % avoids a permanent heating current
through the lamp electrodes during operation.
The load on the fi laments and the power loss are re-
duced by approx. 2 W as a result. “Cut off” is not ac-
tive at low temperatures, which makes operating the
lamp easier for conventional lamps
10)
and amalgam
lamps.
Intelligent temperature management
Power reduction control through the ECG to protect
the electronics in case of excessive ambient temper-
atures
Use is possible in extremely tight, hot lumi-
naires (lifetime, effi ciency increase, approbation)
Note
The ECG measures its internal temperature on the
intermediate circuit capacitor (electrolytic capacitor)
1 x per minute. It begins to reduce the power at
84 °C to lower the internal temperature of the lumi-
naire and maintain the temperature of the electrolytic
capacitor at 84 °C. The t
c
temperature remains be-
tween 75 °C and 80 °C, depending on the installation
conditions (heat coupling from above or below). At
an ambient temperature of 25 °C (in the room, e.g.
of ce), a reduction in the ECG power by 10 % is also
suf cient for hot luminaires. Very little light is lost in
the process because the ef ciency of lamps and EC-
Gs is improving.
Most ef cient energy savings
measure compared to normal operation.
High t
c
point values (t
c
= 75 °C) enable operation at
high ambient temperatures (t
a
values).
Stable dimming operation even in amalgam lamps
(CONSTANT lamps)
Especially suitable for use in
areas with low ambient temperatures (e.g. cold stores,
outdoor areas) or high temperatures
Intelligent power control when detecting instabilities
in the lamp circuit (amalgam lamp start) preserves
the lamp and ECG
Optimized fi lament heating and lamp operation in
case of mains undervoltage (no damage to the lamps)
EOL shutdown after test 2
Asymmetric power test for detecting defective lamp
electrodes or high-impedance lamp sections, e.g.
through leakages in the glass tube
Chip ID (CIN = Chip Identifi cation Number, series num-
ber) for easy system installation
OSRAM DALI magic:
Address allocation is possible via CIN
EEPROM for ensuring settings/parameters even in the
event of power failure
Lamp replacement without mains reset (automatic re-
start of lamps after lamp replacement, including HF
DIM)
DC operation in the input voltage range of 154–276 V/
lamp start above 198 V (i.e. no lamp ignition e.g. at
170 V DC)
Optimized radio interference supression: Compliance
with the required EMC speci cation limits with a com-
fortable safety margin to make it easier to install the lu-
minaire (including HF DIM)
DALI standard according to IEC 62386 - 101/-102/-201
110-V standard according to IEC 60929
8) Valid for OSRAM QUICKTRONIC
®
Intelligent (QTi) DALI/DIM ECG,
exceptions indicated in (…)
9) Special approvals of ECG lamp for QTi-DALI/DIM, HF DIM models
10) Amalgam-free low-pressure gas discharge lamps