Technical data
QUICKTRONIC
®
Intelligent DALI DIM | New properties of QTi DALI
18
3.1.2 Activating the Corridor Function
Activate the Corridor Function by permanently applying the
supply voltage (220 V–240 V) to the DALI input of the ECG
for at least 120 seconds (50 Hz) and 100 seconds (60 Hz),
respectively.
3.1.3 Changing from the Corridor Function to the
Touch DIM Function
It is possible to change from the Corridor Function to the
Touch DIM Function by briefl y pressing a push-button 5
times (at the DALI input, 220 V-240 V) within 3 seconds.
3.1.4 Setting Corridor Function parameters
The Corridor Functions are easily programmable with the
DALI magic/Wizard system (also see DALI magic manual
at: http://www.osram.com/osram_com/tools-and-services/
tools/dali-magic/index.jsp), i.e. the programmed settings
(e.g. extent of the three light ranges, duration of the six time
ranges) remain saved in the DALI ECG.
Three dimming ranges (1…100 %), free parameterization
of time (I…VI) using DALI magic.
Factory-set parameters:
A: 100 %, D0: 120 s, F1: 32 s
B: 10 %, T1: unlimited
3.2 Touch DIM Function
Dim up to 20 DALI ECGs using commercial push-
buttons!
In addition to operation on DALI control units, QTi DALI
ECGs offer the possibility of Touch DIM operation.
The QTi platform now enables up to 20 ECGs to be
dimmed using commercial push-buttons with no problem.
Dimming up to 4 DALI ECGs with one Touch DIM
sensor.
Additional properties are described in chapter 4.2.
A
A
B
B
C
Corridor Function phasing (general and factory setting)
Light value
Light value
230 V
230 V
ON
ON
OFF
OFF
Standby I
DO
DO
I
I
II
II
III
III
IV
IV
VVI
F1
F1
T1
T1
T2F2 Time
Time
Time
Standby II
TOUCH DIM
SENSOR
General curve: Factory setting: