Technical data

QUICKTRONIC
®
Intelligent DALI DIM | New properties of QTi DALI
17
3 New properties of QTi DALI
3.1 Corridor Function and parametrization options
3.1.1 Description
Corridor Function: It is possible to connect the ECG di-
rectly to commercially available motion sensors. The Corri-
dor Function is triggered by a switching signal, i.e. the volt-
age of the supply line (220–240 V, 50/60 Hz) is switched to
the DALI control line inputs (DA, DA; see the diagram be-
low). A preset “out-of-the-box” luminous fl ux program
launches upon triggering. This can be individually adjusted
via OSRAM DALI Wizard and DALI magic. Three light value
ranges and six time ranges are available for this purpose.
Several OSRAM DALI ECGs can be synchronized in an in-
stallation via the frequency of the mains voltage (50/60 Hz).
The maximum number of ECGs in an installation is only lim-
ited by the sum of the inrush current surges from the indi-
vidual ECGs. Additional installation instructions can be
found in chapter 10.8.
Advantage
Development of new applications (stairwells, corridors,
large storage facilities, …) with the possibility for saving
energy and achieving high energy ef ciency.
CORRIDOR
FUNCTION
OSRAM DALI ECG wiring diagram for Corridor Function
L3
T
Motion sensor
PE N L1 L2 L3
L2
L1
N
PE
Lamp
OSRAM DALI ECG
OSRAM DALI ECG
OSRAM DALI ECG
Lamp
Lamp
~
~
~
~
~
~
DA
DA
DA
1
1
1
2
2
2
3
3
3
4
4
4
DA
DA
DA