Technical data
QUICKTRONIC
®
Intelligent DALI DIM | Overview of dimmable control gears
15
2.6 Features and performance characteristics of the
digital interface
—
IEC 62386: This allows devices from different manufac-
turers to be combined. A special feature which should
be noted is that the manufacturers represented in the
DALI Group
5)
are continuously expanding the tests de-
fi ned as standard to guarantee high functional safety.
— Physical user data rate of 1200 bit/s enables a fail-safe
operation
6)
.
— Safe interference voltage distance: Safe operation
is guaranteed as a result of the generously designed in-
terference voltage distance of the high and low levels.
— Data coding: The Manchester code is used; this allows
transmission errors to be recognized through its structure.
— Maximum system current: The maximum current that
a central interface supply
7)
may deliver is 250 mA. Each
control gear may consume max. 2 mA. This must be
taken into account when selecting the interface supply.
— Limited system size: A maximum of 64 control gears
with an individual address can be differentiated in a system.
— Information feedback: ON/OFF, current brightness val-
ue of the connected lamps, lamp status etc. are possible.
— Control and supply lines can be laid together: A
minimum cross section of the line must be taken into
account. The maximum line length between two
connected system participants should not exceed
300 meters.
— Floating control input: The control input is galvanical-
ly separated from the mains voltage (basic insulation,
however, no safety extra-low voltage (SELV)).
Thus, the ECGs may be operated on different external
wires (phases).
— No termination resistors required: The interface
lines must not be completed with resistors.
— Dimming range 1 %-100 % (the lower limit
depends on the lamp and manufacturer): The pro-
gression of the characteristic line is standardized and
adjusted to eye sensitivity (logarithmic characteristic
line). An even impression of brightness results from
standardization when using control gears from different
manufacturers.
— Programmable dimming times: Special settings are
possible, such as the rate of changing the lighting level
(e.g. from 1 % to 100 % dimmer setting).
— Disruption of the data line: Defi ned light settings are
automatically stored.
— Saving lighting scenes (different group-dependent
dimming conditions): Saving up to 16 scenes is pos-
sible.
— Connection to building management systems via
converter: The interface is primarily designed for room
applications; however, it can be integrated into the
building management systems via converters.
— Easy new system confi guration: If the system is set
once and confi gured, changes to the function of the
system, the lighting scene and the lighting functions are
only a matter of confi guration and do not require any
changes to the hardware. Example: Regrouping lumi-
naires in a open-plan offi ce.
— Easy integration of new components. If an existing
lighting system is to be expanded, new components can
be added everywhere within the system. When doing
so, make sure that the system supply is suffi ciently di-
mensioned.
— Polarity-free interface
2.7 Properties of the 1…10-V interface
Note
This chapter refers to OSRAM ECGs, models QTi DIM and
QT DIM, hereafter abbreviated as OSRAM DIM ECG.
— They are controlled via a fail-safe DC voltage signal of
10 V (maximum brightness; open control line) to 1 V
(minimum brightness; control line short-circuited).
— The control power is generated by the ECG
(max. current: 0.6 mA per ECG).
— The voltage on the control line is isolated from the mains
cable (basic insulation), however, without safety extra-
low voltage (SELV).
— ECGs can be dimmed in different phases via the same
control unit.
Note
The following must be observed due to the properties of
the 1…10-V interface:
— All control lines of an ECG installation must be connect-
ed with the correct polarity (+/–).
— The control line is insulated from the mains cable, how-
ever, without safety extra-low voltage (SELV). This
means that cables and terminals must be used for the
installation which are approved for 230 V.
— Using a resistor, the control voltage can easily be limited
up or down; several control units can be combined to-
gether.
5) Every ECG manufacturer that displays the DALI logo on the ECG is
a member of the DALI Group.
6) 40 command/s and 16 bit ➔ 640 bit/s
7) DALI interface on the control unit:
The DALI interface of the control unit also supplies the DALI inter-
face of the connected DALI components. So that the maximum per-
missible total current of 250 mA is not exceeded, no additional DALI
supplies or DALI control units may be connected in this system. In
order to not exceed the maximum permissible voltage drop of 2 V,
the cable cross section must be selected according to the table in
the technical data.