Specifications

SPECIFICATIONS
31
INDOOR UNITS
Ceiling Mounted Duct Type
FXMQ40PVE FXMQ50PVE
4.7
16,000
4,000
5.0
17,100
Galvanised steel plate
4,300
267/216/183
300
X
700
X
700
28
VP25 (External Dia, 32/Internal Dia, 25)
5.8
19,800
5,000
6.3
21,500
5,400
300/275/250
300
X
1,000
X
700
36
4.5 5.6
Heating capacity
kW
Btu/h
kcal/h
/s
External static pressure
Casing
1-phase, 220-240 V/220 V, 50/60 Hz
6.4
12.7
6.4
12.7
Power
consumption
kW
Heating
Cooling
0.194 0.215
0.182 0.203
Airflow rate (HH/H/L)
16/13/11 18/16.5/15m
3
/min
Pa
30-160 50-200
1 1
39/37/35
FXMQ20PVE
2.3
7,800
2,000
2.5
8,500
2,200
150/125/108
300
X
550
X
700
25
2.2
6.4
12.7
0.081
0.069
9/7.5/6.5
30-100
33/31/29
FXMQ25PVE
2.9
9,900
2,500
3.2
10,900
2,800
150/125/108
300
X
550
X
700
25
2.8
6.4
12.7
0.081
0.069
9/7.5/6.5
30-100
33/31/29
FXMQ32PVE
3.7
12,600
3,200
4.0
13,600
3,400
158/133/116
300
X
550
X
700
25
3.6
6.4
12.7
0.085
0.073
9.5/8/7
30-100
34/32/30 41/39/37Sound level (HH/H/L) dB(A)
5751 51 52 59Sound power (H) dB(A)
(*1)
(*2)
MODEL
Power supply
Cooling capacity
kW
Btu/h(*1)
kcal/h(*1)
Drain
Dimensions (H
X
W
X
D)
mm
Machine weight kg
Piping
connections
Liquid (Flare)
Gas (Flare)
mm
111
FXMQ63PVE FXMQ80PVE
FXMQ100PVE FXMQ125PVE
Galvanised steel plate
VP25 (External Dia, 32/Internal Dia, 25)
7.3
24,900
6,300
8.0
27,300
6,900
325/292/267
300
X
1,000
X
700
36
9.5
15.9
9.3
31,700
8,000
10.0
34,100
8,600
417/375/333
300
X
1,000
X
700
36
9.5
15.9
11.6
39,600
10,000
12.5
42,700
10,800
533/450/383
300
X
1,400
X
700
46
9.5
15.9
14.5
49,500
12,500
16.0
54,600
13,800
650/550/466
300
X
1,400
X
700
46
9.5
15.9
7.1 9.0 11.2 14.0
Heating capacity
kW
Btu/h
kcal/h
/s
External static pressure
Casing
1-phase, 220-240 V/220 V, 50/60 Hz
Power
consumption
kW
Heating
Cooling
0.230 0.298 0.376 0.461
0.218 0.286 0.364 0.449
Airflow rate (HH/H/L)
19.5/17.5/16 25/22.5/20 32/27/23 39/33/28m
3
/min
Pa
50-200 50-200 50-200 50-200
1
1 1 1
42/40/38 43/41/39 43/41/39 44/42/40
FXMQ140PVE
16.7
57,000
14,300
18.0
61,400
15,500
766/649/533
300
X
1,400
X
700
47
9.5
15.9
16.0
0.461
0.449
46/39/32
50-140
1
46/45/43Sound level (HH/H/L) dB(A)
60 61 61 62 64Sound power (H) dB(A)
(*1)
(*2)
MODEL
Power supply
Cooling capacity
kW
Btu/h(*1)
kcal/h(*1)
Drain
Dimensions (H
X
W
X
D)
mm
Machine weight kg
Liquid (Flare)
Gas (Flare)
mm
Piping
connections
Note: Specifications are based on the following conditions;
•Cooling: (*1) Indoor temp.: 27°CDB, 19.5°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
(*2) Indoor temp.: 27°CDB, 19°CWB, Outdoor temp.: 35°CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Heating: Indoor temp.: 20°CDB, Outdoor temp.: 7°CDB, 6°CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.
•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
(See Engineering Data Book for details.)
•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
1: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32P), thirteen (FXMQ40P), fourteen (FXMQ50-
125P) or ten (FXMQ140P) levels of control. These values indicate the lowest and highest possible static pressures. The standard static
pressure is 50 Pa for FXMQ20-32P and 100 Pa for FXMQ40-140P.