Specifications

26
Ceiling Suspended
Cassette Type
This thin indoor unit achieves optimum
air distribution, and can be installed
without the need for ceiling cavity
FXUQ71MA
FXUQ100MA
FXUQ125MA
Connection unit
Connection unit is the device for connecting above indoor unit to VRVIII-S.
Depending on installation site requirements or
room conditions, 2-way, 3-way and 4-way
discharge patterns are available.
4-way airflow
from the centre of the store.
The 3-way airflow can distribute
comfortable air throughout the room.
Only one unit is needed to distribute comfortable air
throughout an L-shaped store.
BEVQ-MA
Connection unit for indoor unit
Indoor unit
Piping length*
1
Indoor unit
Remote controller
Super wiring (DIII-NET)
Single-phase 220-240 V
power supply
VRV -S series
outdoor unit
Refrigerant piping layout External wiring layout
Notes:
Gas pipe
Liquid
pipe
Model
Maximum piping length
between the BEV unit
and the indoor unit.
FXUQ-MA 5 m
*1
• When connecting centralised-control device, it is
necessary to install an interface adaptor for an
indoor unit (DTA102A52).
• Connection unit BEVQ-MA is necessary for each
indoor unit.
• The refrigerant piping height difference between
the indoor units and the BEV unit must be within
4 m.
• The BEV unit must be installed within a
maximum height difference between indoor units
of 15 m.
• Branching of the refrigerant piping is not
possible downstream of the BEV unit.
BEVQ71MA/BEVQ100MA/BEVQ125MA