Specifications
Troubleshooting by Indication on the Remote Controller SiUS34-907
178 Troubleshooting
3.38 “U3” Check Operation is not Executed
Remote
Controller
Display
U3
Applicable
Models
RXYMQ36 · 48PVJU
Method of
Malfunction
Detection
Check operation is executed or not
Malfunction
Decision
Conditions
Malfunction is decided when the unit starts operation without check operation.
Supposed
Causes
Check operation is not executed.
Troubleshooting
Press and hold BS4 on the
outdoor master PCB for 5
seconds or more, or turn ON the
local setting mode 2-3 to
conduct a check operation.
Has the
check operation
performed on Outdoor
unit PCB?
Performs the check operation
again and completes the check
operation.
When a leakage detection
function is needed, normal
operation of charging refrigerant
must be completed. Then
start once again and complete a
check operation.
NO
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting the connector, or parts may be damaged.