Service manual

Troubleshooting by Indication on the Remote Controller SiUS28-902_a
89 Troubleshooting
3.4 A6” Indoor Unit: Fan Motor (M1F) Lock, Overload
Remote
Controller
Display
A6
Applicable
Models
All indoor unit models
Method of
Malfunction
Detection
Detection by failure of signal for detecting number of turns to come from the fan motor
Malfunction
Decision
Conditions
When the number of turns cannot be detected even when output voltage to the fan is maximum
Supposed
Causes
Fan motor lock
Disconnected or faulty wiring between fan motor and P.C.B.
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
the connector or parts could be damaged.
Connect the wiring and turn on
again.
Fix the wiring and turn on again.
YES
NO
NO
NO
YES
YES
Replace the indoor unit P.C.B.
Replace the fan motor.
Is the
wiring from the fan
motor securely connected
to connectors on the
indoor unit
P. C . B . ?
Wiring
between the
indoor unit P.C.B. and
fan motor is
disconnected.
Does the fan motor run?