Service manual
SiUS28-902_a Field Setting
Test Operation 48
3.1.2 Wireless Remote Controller - Indoor Unit
BRC7C812
BRC7E83
BRC7E818
1. When in the normal mode, push the button for 4 seconds or more, and operation
then enters the “field set mode.”
2. Select the desired “mode No.” with the button.
3. Pushing the button, select the first code No.
4. Pushing the button, select the second code No.
5. Push the timer button and check the settings.
6. Push the button to return to the normal mode.
(Example)
When setting the filter sign time to “Filter Contamination-Heavy” in all group unit setting, set the
Mode No. to “10”, Mode setting No. to “0” and setting position No. to “02”.