Service manual

Other Control SiUS28-902_a
33 Function
5. Other Control
5.1 Heating Operation Prohibition
Heating operation is prohibited above 82°FDB outdoor air temperature.Outline of Control
(Indoor Unit)
5.2 Drain Pump Control
1. The drain pump is controlled by the ON/OFF buttons (4 button (1) - (4) given in the figure
below).
5.2.1 When the Float Switch is Tripped While the Cooling Thermostat is
ON:
1. (Normal operation):
The objective of residual operation is to completely drain any moisture adhering to the fin of the
indoor unit heat exchanger when the thermostat goes off during cooling operation.
2. (Malfunction residual):
The remote controller will display "A3" and the air conditioner will come to an abnormal stop in 5
minutes if the float switch is turned OFF while the cooling thermostat is ON.
5.2.2 When the Float Switch is Tripped While the Cooling Thermostat is
OFF:
*3. (Malfunction residual):
The remote controller will display "A3" and the air conditioner will come to an abnormal stop if
the float switch is turned OFF and not turned ON again within 5 minutes while the cooling
thermostat is OFF.