Service manual

SiUS28-902_a Protection Control
Function 32
4.4 Inverter Protection Control
Inverter current protection control and inverter fin temperature control are performed to prevent
tripping due to a malfunction, or transient inverter overcurrent, and fin temperature increase.
[Inverter overcurrent protection control]
[Inverter fin temperature control]
Not limited
Inverter current >XA
Inverter current
Inverter current 24.9A
>XA
Inverter
current XA
INV. upper limit frequency
&
10 sec.
15 sec.
Matching of frequency
&
When occurring 3 times within 60 min.,
the malfunction code "
L8
" is output.
When occurring 4 times within 60 min.,
the malfunction code "
L9
" is output.
OR
Limited
INV. upper limit frequency:
1-step down from current
compressor frequency
INV. upper limit frequency:
1-step up from current
compressor frequency
Inverter current
standby
Inverter current XA
continues for 3 min.
Status quo
Without conditions
X
13.7Tb77˚F
12.7Tb<77˚F
Not limited
Tfin179.6˚F
Tfin179.6˚F
Tfin180˚F
Fin temp. standby
Tfin<174.2˚F
INV. upper limit frequency
&
When occurring 3 times within 60 min.,
the malfunction code "
L4" is output.
Limited
INV. upper limit frequency:
1-step down from current
compressor frequency
10 sec.
Matching of frequency
&
Tfin174.2˚F
continues for 3 min.
INV. upper limit frequency:
1-step up from current
compressor frequency
Status quo
Without conditions
15 sec.
OR