Service manual

Basic Control SiUS28-902_a
17 Function
2. Basic Control
2.1 Normal Operation
Cooling Operation
Heating Operation
Heating operation is not functional at an outdoor air temperature of 86°FDB or more.
Actuator Operation Remarks
Compressor Compressor PI control
Used for high pressure protection control, low
pressure protection control, discharge pipe
temperature protection control, and compressor
operating frequency upper limit control with
inverter protection control.
Outdoor unit fan Cooling fan control
Four-way valve OFF
Main electronic expansion valve (EV1) 1400 pls
Subcooling electronic expansion valve
(EV2)
PI control
Hot gas bypass valve (SVP) OFF
This valve turns on with low pressure protection
control.
Receiver gas discharging valve (SVG) OFF
Actuator Operation Remarks
Compressor Compressor PI control
Used for high pressure protection control, low
pressure protection control, discharge pipe
temperature protection control, and compressor
operating frequency upper limit control with
inverter protection control.
Outdoor unit fan STEP8
The fan step changes to STEP1 with high pressure
> 454 psi.
Four-way valve ON
Main electronic expansion valve (EV1) PI control
Subcooling electronic expansion valve
(EV2)
0 pls
Hot gas bypass valve (SVP) OFF
This valve turns on with low pressure protection
control.
Receiver gas discharging valve (SVG) OFF