SiUS28-902 Precautions for New Refrigerant (R-410A)
Precautions for New Refrigerant (R-410A) 176
6. Gauge manifold for R-410A
Specifications
High pressure gauge
15 to 770 psi (-76 cmHg to 53 kg/cm
2
)
Low pressure gauge
15 to 550 psi (-76 cmHg to 38 kg/cm
2
)
•1/4" 5/16" (2min 2.5min)
No oil is used in pressure test of gauges.
For prevention of contamination
Temperature scale indicates the relationship between pressure and temperature in gas
saturated state.
Differences
Change in pressure
Change in service port diameter
7. Charge hose for R-410A
Specifications
Working pressure 737 psi (51.8 kg/cm
2
)
Rupture pressure 3685 psi (259 kg/cm
2
)
Available with and without hand-operated valve that prevents refrigerant from outflow.
Differences
Pressure proof hose
Change in service port diameter
Use of nylon coated material for HFC resistance
(Hose with ball valve)