Service manual

SiUS28-902_a Troubleshooting by Indication on the Unified ON/OFF Controller
Troubleshooting 152
5.2 Display “Under Host Computer Integrate Control” Blinks
(Repeats Single Blink)
Remote
Controller
Display
“under host computer integrated control” (Repeats single blink)
Applicable
Models
Unified ON/OFF controller
Centralized controller, Schedule timer
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Address duplication of centralized remote controller
Improper combination of optional controllers for centralized control
Connection of more than one master controller
Malfunction of transmission between optional controllers for centralized control
Defect of P.C.B. of optional controllers for centralized control