Installation manual

English 8
When an obstruction is present on the air inlet side(2)
4
Z
12 or more
NOTE
Only two outdoor units can be stacked.1.
About 4 in. is required as the drain piping size for the upper 2.
outdoor unit.
Close the area Z (gap between the upper outdoor unit and 3.
the lower outdoor unit) so that the outlet air does not by-
pass there.
(E) When outdoor units are installed in rows (on the roof-
top, etc.)
When one outdoor unit is installed in each row(1)
When two or more outdoor units are installed side (2)
by side
A
L
60 or more
24 or more
120 or more
H
The dimensional relationship between H, L and A is as
shown in the table below.
LA
L H
0 < L 1/2H
10
1/2H < L H
12
H < L
Installation is not allowed.
CAUTIONS ON INSTALLATION5.
Before installation, confi rm the strength and levelness of the
foundation so that vibrations and noise are not generated.
Fix the outdoor unit securely on a rigid base with foundation
bolts as shown in the foundation drawing below.
(Prepare 4 sets of commercially available M12-type or
equivalent foundation bolts, nuts and washers.)
Use resin washers to prevent the paint from being scratched
off and rusting.
The foundation bolts should be protruded by 15/16 in.
(Refer to fi gure)
13/16
Resin
washer
〈〈Drain treatment〉〉
In a location where drain from the outdoor unit may cause
troubles (for example, where drainage may splash on gen-
eral passersby), perform the drain piping work using the
drain plug (optional).
For drain treatment, space of at least 4 in. is required under
the bottom frame of the outdoor unit.
In the drain piping work, make sure that drainage is dis-
charged securely.
(When routing the piping downward, check for water leak-
age.)
5 1/2
1 7/8
5 1/2
24 3/8
Air outlet side
(13 5/8-13 7/8)
13 3/4
11 3/8
8 5/8
4 5/8
Bottom view
(unit: inch)
Drain hole
16 5/8
24 1/8
REFRIGERANT PIPING WORK6.
CAUTION
<To piping technician>
Make sure to open the stop valves after fi nishing the
piping work. (Refer to the table shown in “ 6-7 Additional
refrigerant charge”.)
(Operating the air conditioner with the stop valve shut
may damage the compressor.)
Use R410A to add refrigerant. (The R410A refrigerant
cylinder has a pink stripe painted around it.)
All fi eld piping must be installed by a licensed refrigeration
technician and must comply with relevant local and national
regulations.
BRAZING REFRIGERANT PIPING
Do not use fl ux when brazing copper-to copper refrigerant
piping.
(Particularly for the HFC refrigerant piping) Therefore, use
the phosphor copper brazing fi ller metal (BCuP) which does
not require fl ux.
01_EN_3PA60114-14U.indd 801_EN_3PA60114-14U.indd 8 2/24/2009 5:23:06 PM2/24/2009 5:23:06 PM