Installation manual

3 English
NOTE
Install the indoor and outdoor units, power supply
wiring and transmission wiring at least 3.5ft. away from
televisions or radios in order to prevent image interfer-
ence or noise.
(Depending on the radio waves, a distance of 3.5ft. may not
be enough to eliminate the noise.)
Dismantling of the unit, treatment of the refrigerant, oil
and eventual other parts, should be done in accordance
with the relevant local and national regulations.
Do not use the following tools that are used with con-
ventional refrigerants. (Gauge manifold, charge hose,
gas leak detector, reverse fl ow check valve, refrigerant
charge base, vacuum gauge, refrigerant recovery equip-
ment.)
If the conventional refrigerant and refrigerator oil are mixed
in the R410A, the refrigerant may deteriorated.
Never perform outdoor unit piping connection work
when it is raining.
Safety Precaution
The PCI Data Station is a class A product. In a domestic
environment this product may cause radio interference in
which case the user may be required to take adequate mea-
sures.
INTRODUCTION2.
Standard operation limit2-1
The fi gures below assume following operating conditions for
indoor and outdoor units:
Equivalent pipe length ................25 ft.
Level difference ..........................0 ft.
Cooling Heating
<b>
B
<c>
A
C
D
<a>
0
5
59
115
41
5050
43
70
95
81
50
23
77
60
67 8257
A Outdoor temperature (°FDB)
B Indoor temperature (°FWB)
C Outdoor temperature (°FWB)
D Indoor temperature (°FDB)
Range for continuous operation
Range for pull down operation
Range for warming up operation
Range for operation
Technical specifi cations2-2
(<a> and <b> in the table indicate the operating condition
(shown in the fi gure bottom left).)
Model
RZQ18PVJU RZQ24PVJU RZQ30PVJU
Precaution
Refrigerant
R410A
Power
208-230V 60Hz
[FAQ] Wall mounted
Cooling (MBh)
18 24 <a>
Heating (MBh)
20 26
<b>
[FCQ] Ceiling mounted
Cooling (MBh)
18 24 30 <a>
Heating (MBh)
20 27 34
<b>
[FHQ] Ceiling Suspended
Cooling (MBh)
18 24 30 <a>
Heating (MBh)
20 27 34
<b>
Dimensions
(inch)
30-5/16 × 35 7/16 × 12 5/8
H × W × D
Weight
(lb.) 150
Connections
Gas
(inch)
5/8
Liquid
(inch)
3/8
Electrical specifi cations2-3
(<c> in the table indicate the operating condition (shown in
the fi gure bottom left).)
Model
RZQ18PVJU RZQ24PVJU RZQ30PVJU
Precaution
Power
Phase
~
Frequency (Hz) 60
Voltage (V) 208-230
Voltage
torerance
(%) ±10
Rated current of
fuse
(A) 20
Compressor
Phase 3~
Frequency (Hz) 60
Voltage (V) 208-230
Min. Circuit Amps.
(A) 16.5
<c>
Accessories2-4
Confi rm that the following accessories are supplied.
Clamp Insulation tube
Cover
(Handle)
(Large-1) (Large-2) (Small-1) (Small-2)
(1 pc.) (2 pcs.) (1 pc.) (2 pcs.) (1 pc.)
Screw Conduit mounting plate Others
Installation manual
(1 pc.) (2 pcs.) (2 pcs.)
Main components2-5
For main components and function of the main components,
refer to the Engineering Data Book.
01_EN_3PA60114-14U.indd 301_EN_3PA60114-14U.indd 3 2/24/2009 5:23:04 PM2/24/2009 5:23:04 PM