ESIE05-03 Field settings
Part 4 – Commissioning and Test Run 4–33
3
4
5
1
Capacity When "low humidity application" is selected. Field setting 16(26)-2-03:
Capacity When "low humidity application + freeze up operation prevention" is selected. Field setting
16(26)-2-04:
Note: P Operation range on indoor side expanded from minimum 12°CWB to 11°CWB when using LH
setting.
P Do not use a setpoint below 20°C to avoid operation out of the indoor operation range (11°CWB).
P Be sure to set the indoor fan to high speed.
Outdoor
Temp.
(°C-DB)
Indoor Temp. (°C-WB)
11 14 16 18 19 20 22 24
Capacity (% of standard point)
-15 0.62 0.76 0.86 0.95 1.00 1.02 1.07 1.11
-10 0.62 0.76 0.86 0.95 1.00 1.02 1.07 1.11
-5 0.62 0.81 0.91 1.01 1.06 1.16 1.21 1.26
0 0.620.810.911.011.061.161.211.26
5 0.620.810.911.011.061.161.211.26
10 0.62 0.81 0.91 1.01 1.06 1.16 1.21 1.26
15 0.62 0.81 0.91 1.01 1.12 1.14 1.19 1.24
20 0.62 0.81 0.91 1.07 1.10 1.12 1.16 1.21
25 0.62 0.81 0.91 1.05 1.07 1.09 1.13 1.18
30 0.61 0.81 0.91 1.01 1.04 1.06 1.10 1.14
35 0.61 0.81 0.94 0.98
1.00 1.02 1.06 1.11
40 0.61 0.81 0.90 0.94 0.96 0.98 1.02 1.06
Outdoor
Temp.
(°C-DB)
Indoor Temp. (°C-WB)
11 14 16 18 19 20 22 24
Capacity (% of standard point)
-15 0.51 0.68 0.78 0.95 1.01 1.06 1.16 1.26
-10 0.51 0.68 0.78 0.95 1.01 1.06 1.16 1.26
-5 0.51 0.68 0.78 0.95 1.01 1.06 1.16 1.26
0 0.51 0.68 0.78 0.95 1.01 1.06 1.16 1.26
5 0.51 0.68 0.78 0.95 1.01 1.06 1.16 1.26
10 0.51 0.68 0.78 0.95 1.01 1.06 1.16 1.26
15 0.51 0.68 0.78 0.95 1.01 1.06 1.16 1.24
20 0.51 0.68 0.78 0.95 1.01 1.06 1.16 1.21
25 0.51 0.68 0.78 0.95 1.00 1.06 1.13 1.18
30 0.51 0.68 0.78 0.95 1.00 1.05 1.10 1.14
35 0.51 0.68 0.78 0.95
1.00 1.02 1.06 1.11
40 0.51 0.67 0.78 0.94 0.96 0.98 1.02 1.06