Field settings ESIE05-03
4–32 Part 4 – Commissioning and Test Run
3
1
4
5
Graph 3 Target evaporating temperature control when "low humidity application + freeze up operation
prevention" is selected. Field setting 16(26)-2-04:
Note: RZQ71: Te by LP sensor
RZQ100~140: Te by calculation
Change thermostat
control
In order to increase continuous operation of the unit in low latent heat applications and avoid the rise
of temperature after thermostat OFF, the thermostat control will be changed when using field settings
16(26)-2-03 & 16(26)-2-04.
Thermostat ON
P ∆Trs ≥ 0.5 °C (No change from standard setting)
Thermostat OFF
P ∆Trs ≤ -2.0 °C for 5 minutes continuously.
P ∆Trs ≤ 4.5 °C
Remote controller setting temp.
Te target limitted ≤ 20°C
(to protect the comp.)
Te (see note) target acceptable area
P Indoor temp. > setting → Te target down
P Indoor temp. < setting → Te target up
Te target limitted ≥ 2°C
(not to freeze)
Freeze protection
(40min. integrated coil temp. ≤ -1°C)
Te target acceptable area
Te target
(°C)
Indoor Temp
(°C DB)