Service manual
ESIE05-03 Field settings
Part 4 – Commissioning and Test Run 4–31
3
4
5
1
Graph 2 Target evaporating temperature control when "low humidity application" is selected. Field setting
16(26)-2-03:
Note: RZQ71: Te by LP sensor
RZQ100~140: Te by calculation
Remote controller setting temp.
Te target limitted ≤ 20°C
(to protect the comp.)
Te (see note) target acceptable area
P Indoor temp. > setting → Te target down
P Indoor temp. < setting → Te target up
Te target limitted ≥ 0°C
Freeze protection
(40min. integrated coil temp. ≤ -1°C)
Te target acceptable area
Te target
(°C)
Indoor Temp
(°C DB)