Service manual

Field settings ESIE05-03
4–30 Part 4 – Commissioning and Test Run
3
1
4
5
Graph 1 Target evaporating temperature control in case of factory setting 16(26)-2-01:
Note: RZQ71: Te by LP sensor
RZQ100~140: Te by calculation
Remote controller setting temp.
Te target limitted 20°C
(to protect the comp.)
Te target limitted
Indoor temp. – 11°
(not to rising wetbulb)
Te (see note) target
acceptable area
P Indoor temp. > setting
Te target down
P Indoor temp. < setting
Te target up
Te target limitted 2°C
(not to freeze)
Te target limitted
Indoor temp. – 25°
(not to sweat)
Freeze protection
(40min. integrated coil temp. -1°C)
Indoor Temp
(°C DB)
Te target acceptable area
ESIE05-03.book Page 30 Wednesday, April 6, 2005 4:09 PM