Service manual
ESIE05-03 Field settings
Part 4 – Commissioning and Test Run 4–29
3
4
5
1
Function details
Parameters
Factory setting Low humidity application
setting
Low humidity application +
freeze up operation pre-
vention
Field Setting 16(26)-2-01 16(26)-2-03 16(26)-2-04
Compressor control
P The compressor frequency is controlled in function of the target evaporating temperature.
P The target evaporating temperature is controlled in function of the cooling load.
Minimum target Te = 2°C Minimum target Te = 0°C Initial minimum target Te =
2°C, but can be changed in
function of actual Te, to
avoid freeze up activation:
P Te ≤ -1°C for 20 minutes
accumulated => Change
target Te ≥ 5°C
P Te ≤ -1°C for 30 minutes
accumulated => Change
target Te ≥ 8°C
See graph 1 See graph 2 See graph 3
Freeze protec-
tion function
Start Te ≤ -1°C for 40 minutes
accumulated
OR
Te ≤ A°C for 1 minute
continuous
(Indoor decision)
Te ≤ -1°C for 40 minutes
accumulated
OR
Te ≤ -3°C for 1 minute
continuous
(Outdoor decision)
Te ≤ -1°C for 40 minutes
accumulated
OR
Te ≤ A°C for 1 minute
continuous
(Outdoor decision)
End Te > 7°C for 10 minutes
continuously.
(Indoor decision)
Te > 7°C for 3 minutes
continuously
OR
Te > 4°C for 20 minutes
continuously
(Outdoor decision)
Te > 7°C for 3 minutes
continuously
OR
Te > 4°C for 20 minutes
continuously
(Outdoor decision)
FAQ FHQ All except FAQ & FHQ
A -1°C -3°C -5°C