Service manual

ESIE05-03 Field settings
Part 4 – Commissioning and Test Run 4–27
3
4
5
1
Demand 1 Power consumption limitation in function of setting on DS1:
Demand 2 Power consumption limitation set to 40%.
Demand 3 Forced thermostat OFF.
DS1 SETTING
Maximum Power
Consumption
12
OFF OFF 60%
ON OFF 70%
OFF ON 80%
ON ON 100%
ESIE05-03.book Page 27 Wednesday, April 6, 2005 4:09 PM