Service manual

Field settings ESIE05-03
4–26 Part 4 – Commissioning and Test Run
3
1
4
5
2.12 I-Demand Function
Purpose Set a limitation towards the power consumption from the system.(e.g. budget control, limit power
consumption during peak moments,..)
Setting 3 different demand setting can be selected by using terminal X801M:
P Demand 1 Close contact between COM and contact 1
P Demand 2 Close contact between COM and contact 2
P Demand 3 Close contact between COM and contact 3
Power supply connector
(on outdoor PCB X77A)
Output on X801M =
12VDC, 12mA
Maximum wire length =
100 meter
Transmission connector
(on outdoor PCB X6A)
ESIE05-03.book Page 26 Wednesday, April 6, 2005 4:09 PM