Service manual
ESIE05-03 Troubleshooting
Part 3 – Troubleshooting 3–39
33
4
5
1
1.11 Overview of the Indoor Safety Devices
Thermal protector Thermal fuse fan motor
Abnormal Reset (automatic)
FFQ35~60 >130°C +/-5°C <83°C +/-20°C N.A.
FCQ35~71B >130°C +/-5°C <83°C +/-20°C N.A.
FCQ100/125B >140°C +/-5°C <45°C +/-15°C N.A.
FBQ35~125 N.A. N.A. >152°C
FDQ125 N.A. N.A. >160°C
FHQ35~125 >130°C +/-5°C <83°C +/-20°C N.A.
FUQ71~125 >130°C +/-5°C <83°C +/-20°C N.A.
FAQ71/100 >130°C +/-5°C <83°C +/-20°C N.A.
FCQ71~140D N.A. N.A. N.A.
ESIE05-03.book Page 39 Wednesday, April 6, 2005 4:09 PM