Specifications
Commissioning Manual EM11A021
DCM601A51 intelligent Touch Manager
80
• Inform the user that all units are forced to operate in the cooling mode during leakage check.
• Caution the user not to change the time setting of iTM during leakage check.
• Power consumed by the indoor unit during leakage check is also proportionally distributed.
• Leakage check and power limit control (*) cannot be conducted at the same time.
(i) If power limit control is set to [Demand 3(Forced thermo OFF)], it will be conducted before
leakage control.
(ii) If power limit control is set to [Demand 1,Demand 2], leakage check will be conducted rst.
* In power limit control, a command is sent to the outdoor unit via the outdoor unit external
control adapter (DTA104A
*
*
).
• Leakage check and iTM energy saving control cannot be conducted at the same time.
Leakage check will be conducted before energy saving control.
NOTE