Specifications

Capacity cooling kW
heating kW
Power Input cooling kW
heating kW
Casing material
Dimensions unit height mm
width mm
depth mm
Weight unit kg
Heat Exchanger dimensions nr of rows
fin pitch mm
face area m
2
nr of stages
fin fin type
Fan type
air flow rate cooling medium m
3
/min
heating medium m
3
/min
external static pressure standard Pa
motor model
output (high) W
drive
Piping liquid (OD) type
connections diameter mm
gas type
diameter mm
drain diameter mm
heat insulation
Air Filter
Refrigerant control
Temperature control
Safety devices
Safety devices
Power Supply frequency Hz
voltage V
Current minimum circuit amps (MCA) A
maximum fuse amps (MFA) A
full load amps (FLA) A
Voltage range minimum V
maximum V
KH=;A>A;9LAGFK
>PEI%E>N)
FXM Q200-250M FV1
Ventilation
FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1
14.0 22.4 28.00
8.9 13.9 17.40
0.359 0.548 0.638
0.359 0.548 0.638
Galvanised steel Galvanised steel Galvanised steel
470 470 470
744 1380 1380
1100 1100 1100
86 123 123
3 3 3
2.00 2.00 2.00
0.28 0.65 0.65
26 26 26
Cross fin coil Cross fin coil Cross fin coil
Sirocco fan Sirocco fan Sirocco fan
18.0 28.0 35.0
18.0 28.0 35.0
185 225 205
D13/4G2DA1 D13/4G2DA1 D13/4G2DA1
380 380 380
Direct drive Direct drive Direct drive
Flare connection Flare connection Flare connection
9.5 9.5 9.5
Flare connection Brazing/Brazing connection Brazing/Brazing connection
15.9 19.1 22.2
PS1B PS1B PS1B
Glass fiber Glass fiber Glass fiber
As option As option As option
Electronic expansion valve Electronic expansion valve Electronic expansion valve
Microprocessor thermostat for cooling and heating Microprocessor thermostat for cooling and heating Microprocessor thermostat for cooling and heating
Fuse Fuse Fuse
Fan motor thermal protector Fan motor thermal protector Fan motor thermal protector
50 50 50
220-240 220-240 220-240
1.90 3.30 3.80
15 15 15
1.50 2.60 3.00
-10% -10% -10%
10% 10% 10%
Notes:
Nominal cooling capacities are based on : outdoor temperature : 33°CDB, 28°CWB (68%RH), discharge set temperature : 18°CDB, equivalent piping length 7.5m (horizontal)
Nominal heating capacities are based on : outdoor temperature : 0°CDB, -2.9°CWB (50%RH), discharge set temperature : 25°CDB, equivalent piping length 7.5m (horizontal)
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its colorimetric method(gravity method) 50% or more.
Voltage range : units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%.
MCA/MFA : MCA = 1.25 x FLA
MFA <= 4 x FLA
Next lower standard fuse rating minimum 15A
Select wire size based on the MCA
Instead of a fuse, use a circuit breaker