Specifications
EDUS04-740 Electric Characteristics
Room Air Conditioners D-Series 29
10.Electric Characteristics
3D056378
Representative Unit Combination Power Supply COMP OFM IFM
Indoor Unit Outdoor Unit Hz-Volts Voltage Range MCA MFA RLA W FLA W FLA
FTXS09DVJU RX09FVJU
60-208
MAX. 60Hz 253V
MIN. 60Hz 187V
6.1 15
5.1
31 0.2 18
0.2
60-230 4.6 0.18
FTXS12DVJU RX12FVJU
60-208
MAX. 60Hz 253V
MIN. 60Hz 187V
7.9 15
6.7
31 0.2 18
0.2
60-230 6.0 0.18
FTXS15DVJU RX15FVJU
60-208
MAX. 60Hz 253V
MIN. 60Hz 187V
13.7 20
11.8
53 0.24 43
0.2
60-230 10.7 0.18
FTXS18DVJU RX18FVJU
60-208
MAX. 60Hz 253V
MIN. 60Hz 187V
14.1 20
12.2
53 0.24 43
0.2
60-230 11.0 0.18
FTXS24DVJU RX24FVJU
60-208
MAX. 60Hz 253V
MIN. 60Hz 187V
15.8 20
13.6
53 0.26 43
0.22
60-230 12.3 0.2
Symbols: Note:
MCA : MIN. CIRCUIT AMPS (A) 1. RLA is based on the following conditions.
Indoor temp. 80°FDB/67°FWB
Outdoor temp. 95°FDB/75°FWB
2. Maximum allowable voltage variation between phases is 2%.
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. Be sure to install an earth leak detector. (One that can handle
higher harmonics.)
(This unit uses an inverter, which means that it must be used an
earth leak detector capable handling high harmonics in order to
prevent malfunctioning of the earth leak detector itself.)
MFA : MAX. FUSE AMPS (A)
RLA : RATED LOAD AMPS (A)
OFM : OUTDOOR FAN MOTOR
IFM : INDOOR FAN MOTOR
FLA : FULL LOAD AMPS (A)
W : FAN MOTOR RATED OUTPUT (W)
RHz : RATED OPERATING FREQUENCY (Hz)