Spec Sheet

Daikin North America LLC 5151 San Felipe, Suite 500 Houston, TX 77056
(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without
notice and without incurring any obligations)
Submittal Revision Date: December 2018 Page 1 of 4
Performance
Cooling (Btu/hr)
Rated (Min/Max) 14,400 (5,100 / 17,400)
Sensible @ AHRI 11,690
Standard Operating Range 50°F – 115°F
Extended Operating Range* -4°F – 115°F
Rated Cooling Conditions:
Indoor: 80°F DB/67°F WB
Outdoor: 95°F DB/75°F WB
*With field settings and wind baffle
Heating (Btu/hr)
1: @ 47° Rated (Min/Max) 18,000 (5,600 / 18,500)
2: @ 17° Rated 11,500
3: @ 5° 8,040
Operating Range 5°F – 65°F
1:
Rated Heating Conditions:
Indoor: 70°F DB/60°F WB
Outdoor: 47°F DB/43°F WB
2: Rated Heating Conditions:
Indoor: 70°F DB/60°F WB
Outdoor: 17°F DB/15°F WB
3:
Indoor: 70°F DB/60°F WB
Outdoor: 5°F DB/5°F WB
Submittal Data Sheet FDMQ15RVJU / RX15RMVJU
1.25-Ton Ducted Concealed Heat Pump System
Efficiency
Cooling Heating
SEER 20.2 HSPF 10.3
EER 12.7 COP 3.8
Electrical
208/60/1 230/60/1
System MCA 9.7 9.7
System MFA 15 15
Compressor RLA 8.0 8.0
Outdoor fan motor FLA .31 .31
Outdoor fan motor W 91 91
Indoor fan motor FLA .87 .87
Indoor fan motor W 230 230
MFA: Max. fuse amps MCA: Min. circuit amps (A) FLA: Full load amps (A)
RLA: Rated load amps (A) W: Fan motor rated output (W)
Piping
Liquid (in) 1/4
Gas (in) 1/2
Drain (in) 1
Max. Interunit Piping Length (ft) 98.5
Max. Interunit Height Difference (ft) 65.6
Chargeless (ft) 32.8
Additional Charge of Refrigerant (oz/ft) .21
Indoor Specifications
Airflow Rate (cfm)
Cooling Heating
H M H M
516 438 516 438
L L
360 360
Sound (dBA) 34 34
Dimensions (H × W × D) (in) 9-5/8 × 39-3/8 × 31-1/2
Airflow Inlet (H x W) (in) 8-3/16 x 37-1/2
Weight (Lbs) 77
Outdoor Specifications
Compressor Hermetically Sealed Swing Type
Refrigerant R-410A
Factory Charge (Lbs) 2.49
Refrigerant Oil PVE (FVC50K)
Airflow Rate (cfm)
Cooling
Heating
2,313
2,108
Sound Pressure Level (dBA) 50 / 51
Dimensions (H × W × D) (in) 28-15/16 × 34-1/4 × 12-5/8
Weight (Lbs) 97
Job Name:
Tag#
Complete warranty details available from your local dealer or at
www.daikincomfort.com. To receive the 12-Year Parts Limited
Warranty, online registration must be completed within 60 days of
installation. Online registration is not required in California or Quebec.
If product is installed in a commercial application, limited warranty
period is 5 years
.

Summary of content (4 pages)