Specifications
Field Setting from Outdoor Unit SiBE341027
76 Test Operation
21
Refrigerant
recovery/vacuuming
mode setting
khkhkhk
Refrigerant recovery / vacuuming: OFF
khhhhhk ∗
Refrigerant recovery / vacuuming: ON
khhhhkh
22
Low night noise
setting
khkhkkh
OFF
khhhhhh ∗
Level 1 (outdoor fan with 6 step or lower)
khhhhhk
Level 2 (outdoor fan with 5 step or lower)
khhhhkh
Level 3 (outdoor fan with 4 step or lower)
khhhhkk
25
Setting of external
low noise level
khkkhhk
Level 1 (outdoor fan with 6 step or lower)
khhhhhk
Level 2 (outdoor fan with 5 step or lower)
khhhhkh ∗
Level 3 (outdoor fan with 4 step or lower)
khhhkhh
26
Low night noise
operation start
setting
khkkhkh
About 20:00
khhhhhk
About 22:00
khhhhkh ∗
About 24:00
khhhkhh
27
Low night noise
operation end
setting
khkkhkk
About 6:00
khhhhhk
About 7:00
khhhhkh
About 8:00
khhhkhh ∗
28
Power transistor
check mode
khkkkhh
OFF
khhhhhk ∗
ON
khhhhkh
29
Capacity priority
setting
khkkkhk
OFF
khhhhhk ∗
ON
khhhhkh
30 Demand setting 1
khkkkkh
60 % demand
khhhhhk
70 % demand
khhhhkh ∗
80 % demand
khhhkhh
32
Normal demand
setting
kkhhhhh
OFF
khhhhhk ∗
ON
khhhhkh
35
Setting of difference
in height for the
outdoor unit
kkhhhkk
Normal
khhhhhh ∗
65 m or less
khhhkhk
38
Emergency
operation
(Master unit with
multi-outdoor-unit
system is inhibited to
operate.)
kkhhkkh
OFF
khhhhhk ∗
Master unit operation: Inhibited
khhhhkh
39
Emergency
operation
(Slave unit 1 and 2
with multi-outdoor-
unit system is
inhibited to operate.)
kkhhkkk
OFF
khhhhhk ∗
Slave unit 1 operation: Inhibited
khhhhkh
40
Emergency
operation
(Slave unit 3 with
multi-outdoor-unit
system is inhibited to
operate.)
kkhkhhh
OFF
khhhhhk ∗
Slave unit 2 operation: Inhibited
khhhhkh
55
Master-slave set-up
for multi outdoor
units
kkkhhkk
Automatic judgement
khhhhhh ∗
Master
khhhhhk
Slave 1
khhhhkh
Slave 2
khhhhkk
Slave 3
khhhkhh
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory set