Specifications

SiBE341027 Test Operation
Test Operation 65
Check operation ends.
(Abnormal termination)
(Completed normally)
hkkhhhh
hhkhhhh
Check the error code on
the indoor unit remote
controller, and follow the
instructions in
"Troubleshooting" to
correct the trouble.
After checking that the LED
display is normal, press the
TEST button (BS4) again.
hlhhkkh
hlhhkkk
hlhkhhh
Waits for conditions to stabilize after restart.
Contamination operation (30 ~ 60
minutes)
Up to 1 hour may be required.
Automatic judgement of piping
length (approximately 10 minutes)
Checks the local piping length.
At the same time, performs a final check of the
refrigerant amount.
* To cancel check operation before it is completed, press the RETURN button (BS3).
Close the refrigerant
cylinder valve.